Options/Accessories
6.1.3.1 Switching from External Bypass to Normal UPS Operation
Action
1.Turn the input switch (Q002) to position ”0“
2.Open the UPS front door and press the green "ON” key
Display shows
** System OFF **
Normal operation
load power %
3. Press  on the keyboard
 on the keyboard
4. Press  or
 or  on the keyboard until
 on the keyboard until
| 5. Press | on the keyboard | 
6.Press  on the keyboard
 on the keyboard
7.Check lamp indication on the bypass panel
8.Turn the output switch (Q002) to position ”1“
9.Turn the bypass switch (Q003) to position ”0“
10.Press  on the keyboard
 on the keyboard
11.Press  or
 or  on the keyboard until
 on the keyboard until
| 12. Press | on the keyboard | 
11.Press  on the keyboard
 on the keyboard
11.Press 
 on the keyboard
 on the keyboard
Bypass operation :NO
Bypass operation :YES
Lamp indication
on Servive Bypass Panel
The Green lamp (H002) above the output switch handle (Q002) lights
Now also the green lamp (H003) above the bypass switch handle (Q003) lights
Only the Green lamp (H003) above the bypass switch handle (Q003) lights
Display shows
Bypass operation :YES
Bypass operation :NO
Normal operation load power xx %
No lamps on the Service Bypass Panel light any longer
| 44 | Installation Guide APC Silcon 480kW 400V UPS |