American Power Conversion 480kW 400V manual Switching from External Bypass to Normal UPS Operation

Page 44

Options/Accessories

6.1.3.1 Switching from External Bypass to Normal UPS Operation

Action

1.Turn the input switch (Q002) to position ”0“

2.Open the UPS front door and press the green "ON” key

Display shows

** System OFF **

Normal operation

load power %

3. Press on the keyboard

4. Press or on the keyboard until

5. Press

on the keyboard

6.Press on the keyboard

7.Check lamp indication on the bypass panel

8.Turn the output switch (Q002) to position ”1“

9.Turn the bypass switch (Q003) to position ”0“

10.Press on the keyboard

11.Press or on the keyboard until

12. Press

on the keyboard

11.Press on the keyboard

11.Press on the keyboard

Bypass operation :NO

Bypass operation :YES

Lamp indication

on Servive Bypass Panel

The Green lamp (H002) above the output switch handle (Q002) lights

Now also the green lamp (H003) above the bypass switch handle (Q003) lights

Only the Green lamp (H003) above the bypass switch handle (Q003) lights

Display shows

Bypass operation :YES

Bypass operation :NO

Normal operation load power xx %

No lamps on the Service Bypass Panel light any longer

990-4059

44

Installation Guide APC Silcon 480kW 400V UPS

Image 44
Contents 480kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 480kW 400V UPSSafety Symbols used in this manual Introduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mm 480kW 1800 19002 1600mm Cabinet for 480kW Isolation Transformer Footprint1 1900mm Cabinet for 480kW UPS Connecting the UPS External ConnectionExternal Connection Right side viewSystem Integration Interface External Connection Connections Terminal Blocks X003/X004 Anxiliary Contacts X005 Output RelaysParallel Board Parallel BoardPower Cables External Control CablesRelay Board RelaysRelay Number Message Alarm-trigging Events Relay Board/Relay FunctionsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Safety Warnings APC Silcon Triple ChassisProduct Description Monitoring PortOptional Power Input Installing Management PeripheralsLEDs If the LED is… Then the Silcon Triple Chassis…Installing Management Peripheral Cards Order of Management Peripheral CardsManagement Peripheral Priority Position Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA If Problems Persist TroubleshootingProblem Possible Cause Solution Product Specifications Monitoring Port Pin Assignments External Connection Power, Physical, and Environmental Specifications SpecificationAPC Silcon Battery Cabinets Important Safety InstructionsSilcon Battery Breaker Box/Fuse-boxInstallation of Batteries Battery Breaker Box Ampere Connection Max Dimensions Weight Rating Cable APC Battery Breaker Box Connection Diagram 120-480kWHxWxD mm CircuitExternal Connection Parameter Setting Comments Programming ParametersProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleProgramming Parameters Service Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories Options/Accessories On Service Bypass Panel ActionDisplay shows Lamp indicationSwitching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Action H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Isolating One UPS for Service/Maintenance Switching Back to Normal Parallel/Redundant OperationIntersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Connections Without Converter Host DTE Remote Display DTEConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Remote Display CablesCommunication Fault Remote Display SettingAlarms Remote Display UseHeight Width Depth Weight Isolation TransformerIsolation 540kVA 480kW 1800 1400 2550Example of Transformer Configuration Yyno Connecting Isolation Transformer External External PE540kW 1000 200Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate APC Denmark