Options/Accessories
NOTICE!
Make sure that gland plate is installed in bottom of cabinet.
CAUTION!
At 100% switch mode load, neutral must be rated for 200% phase current.
62 | Installation Guide APC Silcon 480kW 400V UPS |
NOTICE!
Make sure that gland plate is installed in bottom of cabinet.
CAUTION!
At 100% switch mode load, neutral must be rated for 200% phase current.
62 | Installation Guide APC Silcon 480kW 400V UPS |