American Power Conversion 480kW 400V manual System Configuration Parameters password protected

Page 35

Programming Parameters

System Configuration Parameters (password protected)

Parameter

Setting*

Comments

 

 

 

Enter System no.

380, 400, 415

Optional selection of voltage

Voltage L-L

 

 

 

 

 

System Frequency

50/60

Optional selection of frequency

 

 

 

Isolation Transformer Input

YES, NO

YES if optional input isolation transformer is available

 

 

 

IsolationTransformer

YES, NO

YES if optional output isolation transformer is available

Output

 

 

 

 

 

Delta Soft Start Time

1, 10, 20, 40 sec.

Input current switching in ramp function. Use higher

 

 

values for smaller/unstable diesel generators

 

 

 

External SSW present

YES, NO

YES for systems with external static bypass switch

 

 

 

Normal Charge Voltage

410-460V

Setting of float charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Boost Charge Voltage

438-460V

Setting of boost charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Low Battery warning

336-384V

Discharged Battery warning

 

336V

 

 

 

 

Low Battery shut-down

310-336V

Switches off system at min. permissible battery

 

326V

voltage

 

 

 

Synchronization

0.25, 0.5, 1, 2, 4

Syncronization speed.

 

Hz/sec.

 

 

 

 

High Battery Temperature

15-40°C

Alarm - Ambient temperature for battery too high

 

35°C

 

 

 

 

Common fault delay

0, 10, 20,

Delay before common fault alarm relay is activated

 

30 sec.

 

 

 

 

Reset operation mode lock

YES, NO

YES resets system locked in bypass or battery

 

 

operation mode caused by system failures (only

 

 

applicable for service personnel)

 

 

 

Expected back-up time

0.1-999.9

Expected UPS back-up time in minutes when running

(min.)

5.0

at 100% ohmic load. Time used by ABM**

 

 

 

Battery Capacity in (Ah)

0.1-999.9

Total Battery capacity in Ah.

 

7.0

Setting used by ABM**.

 

 

 

Highest Station Address

2-9

Highest station address in parallel system

 

 

 

Station Address

1-9

Station address in parallel system

 

 

 

APM Mode Active

Disabled

Use only in parallel systems.

(Advanced Power

Redundant +1

Disabled: Advanced power management off.

Management)

Parallel +1

Redundant +1: Redundant operation with one unit

 

 

being inactive in parallel system

 

 

Parallel +1: Redundant operation with all units in

 

 

operation.

 

 

 

APM Test Mode Active

YES, NO

YES, if APM test mode is active

 

 

 

Battery Connection

Common,

Common: if common battery is used in parallel system.

 

Separate

Separate: if separate battery is used

 

 

 

*Bold text refers to factory standard setting **Advanced Battery Monitor

990-4059

Installation Guide APC Silcon 480kW 400V UPS

35

Image 35
Contents 480kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 480kW 400V UPSSafety Symbols used in this manual Tools IntroductionIntroduction Tools and EquipmentUnpacking UnpackingHeight mm Width mm Depth mm 480kW 1800 1900 InstallationInstallation Requirements on Site2 1600mm Cabinet for 480kW Isolation Transformer Footprint1 1900mm Cabinet for 480kW UPS Right side view Connecting the UPSExternal Connection External ConnectionSystem Integration Interface External Connection Connections X005 Output Relays Terminal Blocks X003/X004 Anxiliary ContactsParallel Board Parallel BoardExternal Control Cables Power CablesRelays Relay BoardRelay Board/Relay Functions Relay Number Message Alarm-trigging EventsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Monitoring Port Safety WarningsAPC Silcon Triple Chassis Product DescriptionIf the LED is… Then the Silcon Triple Chassis… Optional Power InputInstalling Management Peripherals LEDsDaisy-chaining the APC Silcon Triple Chassis Installing Management Peripheral CardsOrder of Management Peripheral Cards Management Peripheral Priority Position CardManagement Peripheral Draw mA If Problems Persist TroubleshootingProblem Possible Cause Solution Product Specifications Monitoring Port Pin Assignments External Connection Specification Power, Physical, and Environmental SpecificationsImportant Safety Instructions APC Silcon Battery CabinetsSilcon Battery Breaker Box/Fuse-boxInstallation of Batteries Battery Breaker Box Circuit Ampere Connection Max Dimensions Weight Rating CableAPC Battery Breaker Box Connection Diagram 120-480kW HxWxD mmExternal Connection Parameters Parameter Setting CommentsProgramming Parameters Programming ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Programming Parameters Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorProgramming Parameters Service Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories Options/Accessories Lamp indication On Service Bypass PanelAction Display showsLamp indication On Servive Bypass Panel Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories Options/Accessories Action H002a Lamp indication On Service Bypass Panel Following can be carried out on any UPS Switching Back to Normal Parallel/Redundant Operation Isolating One UPS for Service/MaintenanceIntersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Pin Connections for cable from host to ME800A-R2 Host Connections Without ConverterHost DTE Remote Display DTE Connections With ConverterRemote Display Cables Remote Display Power SupplyRemote Display Use Communication FaultRemote Display Setting Alarms540kVA 480kW 1800 1400 2550 Height Width Depth WeightIsolation Transformer IsolationExample of Transformer Configuration Yyno 1000 200 Connecting Isolation TransformerExternal External PE 540kWOptions/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Dimensions / Weight System SpecificationsSystem Specifications Technical DataAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix APC Denmark How to Contact APCHow to Contact APC APC Corporate