American Power Conversion 2200XLT Replacing the Battery, Storage Conditions, Extended storage

Page 17

Storage

Storage Conditions

Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least two hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery.

Extended storage

At -15 to +30 °C (+5 to +86 °F), charge the UPS’s battery every six months.

At +30 to +45 °C (+86 to +113 °F), charge the UPS’s battery every three months.

Replacing the Battery

This UPS has an easy to replace hot-swappable battery. Battery replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and loads on for the following procedure. See your dealer or call the number listed under APC Contact Information, page 19, for information on replacement battery cartridges.

Note:

Please read the cautions in the Safety section at the beginning of this User’s Manual.

Once the battery is disconnected, the loads are not protected from power outages.

Model Number

Replacement Battery Cartridge (RBC) #

SU1400XLTNET

RBC 11

 

 

SU2200XLTNET

RBC 11

 

 

SU3000TNET

RBC 11

 

 

SU5000T

RBC 12

 

 

SU1400RMXLTNET

RBC 11

 

 

SU2200RMXLTNET

RBC 11

 

 

SU3000RMT3U

RBC 12

 

 

SU5000RMT5U

RBC 12

 

 

11

990-7031C, Revision 4 12/99

Image 17
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Replacement and Recycling of Batteries Handling SafetyElectrical Safety Page Table of Contents Page How to Unpack the SU 5000 UPS ContentsIntroduction UnpackingInstalling Rack Mount Units InstallationPlacement Determine the Location of the UPS in the Rack Rack Mount Options Load the UPS into the RackTower Units Connect the Batteries5U Rack Mount Units 3U Rack Mount UnitsRear Views Initial StartupConnect Ground Leads to Tvss Connector Optional Charge the batteryBattery Pack Connector Optional Low Battery Warning IntervalOperating Instructions Load Bar Graph Low BatteryOverload SmartTrimStorage Replacing the BatteryStorage Conditions Extended storageBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units How to Determine On-Battery Run Time User Configuration ItemsTypical On-Battery Runtime Versus Load, in Hours Tower and 5U Models 1400VA and 2200VA ModelsLoad VA Internal Battery VA w/ 1 Battery Pack Typical On-Battery Run Time Versus Load, in HoursTower and 5U Rack Mount Models 3000 & 5000 VA Models 3U Rack Mount Models 2200 & 3000 VA Models1400 VA 2200 VA 3000 VA 5000 VA SpecificationsTroubleshooting Limited Warranty ServiceIf the UPS requires service do not return it to the dealer APC Contact InformationAppendix a XL Information XL InstallationClick on Configuration Click on UPS Operating Parameters Smart-UPS Battery ProtocolUse the Smart-UPS Battery Pack Utility Battpack To see the change in number of external battery packs Rack Type Hole Type Hardware Required Hardware Included RacksAppendix C Transporting Your Smart-UPS