American Power Conversion 3000T, 5000T, 2200XLT, 1400XLT Appendix a XL Information, XL Installation

Page 26

Appendix A: XL Information

When used with external battery packs, the extended run (XL) UPS offers longer run times than a standard UPS and extra load protection during battery replacement. When replacing the batteries either in the UPS or battery pack(s), the UPS can still respond to a power disturbance using the remaining connected batteries. Please refer to the main sections of this User’s Manual for basic information about the UPS. This appendix provides additional information needed to use extended run versions of the UPS.

XL Installation

This figure shows the location of the battery pack connector on the 5U SU1400RMXL (top), the SU3000 tower unit (right), the 5U SU3000RM (bottom), and the SU1000XL tower unit (left). Some UPS models have the battery pack connector in different positions, but the size and shape of the connector is always the same.

Battery pack connectors are color coded as shown in the table below. Battery pack connectors are also keyed to prevent improper connection. Do not try to install battery packs with connectors that are a different color from the battery pack connector in the UPS.

This UPS

Voltage

Uses this Battery Pack (connector color)

Maximum Number of Battery Packs

SU700XL

 

 

 

SU1000XL

24 VDC

SU24XLBP (gray)

10

SU1400XLT

 

 

 

SU2200XL

48 VDC

SU48XLBP (blue)

10

SU2200XLT

 

 

 

SU3000

 

 

 

SU3000T

48 VDC

SU48BP (red)

1

SU3000RM

 

 

 

SU1400RMXL

 

 

 

SU1400RMXLT

 

 

 

SU2200RMXL

48 VDC

SU48RMXLBP(blue)

5

SU2200RMXLT

 

 

 

Install up to the maximum number of battery packs per XL model UPS following the instructions below.

Note: The 3000 VA UPS accepts only one battery pack.

1. Prepare the UPS to connect the battery

3. Holding the clamp aside, insert the

pack(s). Note the holes used to attach the

battery pack connector into the UPS.

battery pack connector clamp (near the

 

center of the connector opening). Use a

 

#2 Phillips head screwdriver to remove

 

the battery pack connector clamp from the

 

back of the UPS.

 

2. Turn the clamp over and loosely attach

4. Secure the connector clamp.

one end at the edge of the connector

 

opening in the UPS.

 

Correctly completed XL installation with two battery packs.

For additional battery packs, repeat this procedure using the battery pack

connectors on the battery packs.

Caution: Do not stack battery packs. Stacking results in a tipping hazard.

990-7031C, Revision 4 12/99

20

Image 26
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Replacement and Recycling of Batteries Handling SafetyElectrical Safety Page Table of Contents Page Introduction ContentsHow to Unpack the SU 5000 UPS UnpackingInstalling Rack Mount Units InstallationPlacement Determine the Location of the UPS in the Rack Load the UPS into the Rack Rack Mount OptionsConnect the Batteries Tower Units3U Rack Mount Units 5U Rack Mount UnitsInitial Startup Rear ViewsBattery Pack Connector Optional Charge the batteryConnect Ground Leads to Tvss Connector Optional Low Battery Warning IntervalOperating Instructions Overload Low BatteryLoad Bar Graph SmartTrimStorage Conditions Replacing the BatteryStorage Extended storageBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units Typical On-Battery Runtime Versus Load, in Hours User Configuration ItemsHow to Determine On-Battery Run Time Tower and 5U Models 1400VA and 2200VA ModelsTower and 5U Rack Mount Models 3000 & 5000 VA Models Typical On-Battery Run Time Versus Load, in HoursLoad VA Internal Battery VA w/ 1 Battery Pack 3U Rack Mount Models 2200 & 3000 VA ModelsSpecifications 1400 VA 2200 VA 3000 VA 5000 VATroubleshooting If the UPS requires service do not return it to the dealer ServiceLimited Warranty APC Contact InformationXL Installation Appendix a XL InformationClick on Configuration Click on UPS Operating Parameters Smart-UPS Battery ProtocolUse the Smart-UPS Battery Pack Utility Battpack To see the change in number of external battery packs Racks Rack Type Hole Type Hardware Required Hardware IncludedAppendix C Transporting Your Smart-UPS