Troubleshooting

Use the chart below to solve minor UPS installation problems. Contact APC Technical Support Staff for assistance with complex UPS problems. See APC Contact Information, page 19, for a location near you.

Problem and Possible Cause

 

Solution

 

 

 

UPS will not turn on.

 

 

• ON button not pushed.

 

Press the ON button once to power the UPS and the load.

 

• UPS not connected to AC power supply.

 

Check that the power cable from the UPS to the power supply is

 

 

securely connected at both ends.

• UPS input circuit breaker tripped.

 

Reduce the load on the UPS by unplugging equipment and reset the

 

 

circuit breaker (on back of UPS) by pressing the plunger back in.

• Very low or no utility voltage.

 

Check the AC power supply to the UPS with a table lamp. If very

 

 

dim, have the utility voltage checked.

• Battery not connected properly.

 

Confirm the battery connections.

 

 

 

UPS will not turn off.

 

 

• Internal UPS fault.

 

Do not attempt to use the UPS. Unplug the UPS and have it

 

 

 

serviced immediately.

 

 

 

UPS operates on-battery although normal line voltage exists.

• UPS’s input circuit breaker tripped.

 

Reduce the load on the UPS by unplugging equipment and reset the

 

 

 

circuit breaker (on back of UPS) by pressing the plunger back in.

• Very high, low, or distorted line voltage.

 

Move the UPS to a different outlet on a different circuit.

Inexpensive fuel powered generators can distort

 

Test the input voltage with the utility voltage display. If acceptable

the voltage.

 

 

to the load, reduce the UPS’s sensitivity. Refer to Voltage

 

 

Sensitivity, page 8, for instructions.

UPS beeps occasionally.

 

 

• Normal UPS operation.

 

None. The UPS is protecting the load.

 

 

 

UPS does not provide expected backup time.

 

 

• The UPS’s battery is weak due to recent outage

 

Charge the battery. Batteries require recharging after extended

or is near the end of its service life.

 

outages. Also, they wear faster when put into service often or

 

 

when operated at elevated temperatures. If the battery is near the

 

 

end of its service life, consider replacing the battery even if the

 

 

replace battery indicator is not yet lit.

• The UPS is overloaded.

 

Check the UPS’s load display. Unplug less needed equipment, such

 

 

as printers.

Front panel indicators flash sequentially.

 

 

• The UPS has been shut down by remote control.

 

None. The UPS will restart automatically when utility power

 

 

 

returns.

 

 

 

All indicators are lit and UPS emits a constant beeping.

• Internal UPS fault.

 

Do not attempt to use the UPS. Turn the UPS off and have it

 

 

 

serviced immediately.

 

 

 

All indicators are off and UPS is plugged into wall outlet.

• The UPS is shut down and the battery is

 

None. The UPS will return to normal operation when the power is

discharged from an extended outage.

 

restored and the battery has a sufficient charge.

 

 

 

The replace battery light is lit.

 

 

• Weak batteries.

 

Do another self test to see if it clears.

 

• Replacement batteries not connected properly.

 

Confirm the battery connections.

 

 

 

990-7031C, Revision 4 12/99

18

Image 24
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Handling Safety Electrical SafetyReplacement and Recycling of Batteries Page Table of Contents Page Contents How to Unpack the SU 5000 UPSIntroduction UnpackingInstallation PlacementInstalling Rack Mount Units Determine the Location of the UPS in the Rack Load the UPS into the Rack Rack Mount OptionsConnect the Batteries Tower Units3U Rack Mount Units 5U Rack Mount UnitsInitial Startup Rear ViewsCharge the battery Connect Ground Leads to Tvss Connector OptionalBattery Pack Connector Optional Low Battery Warning IntervalOperating Instructions Low Battery Load Bar GraphOverload SmartTrimReplacing the Battery StorageStorage Conditions Extended storageBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units User Configuration Items How to Determine On-Battery Run TimeTypical On-Battery Runtime Versus Load, in Hours Tower and 5U Models 1400VA and 2200VA ModelsTypical On-Battery Run Time Versus Load, in Hours Load VA Internal Battery VA w/ 1 Battery PackTower and 5U Rack Mount Models 3000 & 5000 VA Models 3U Rack Mount Models 2200 & 3000 VA ModelsSpecifications 1400 VA 2200 VA 3000 VA 5000 VATroubleshooting Service Limited WarrantyIf the UPS requires service do not return it to the dealer APC Contact InformationXL Installation Appendix a XL InformationSmart-UPS Battery Protocol Use the Smart-UPS Battery Pack Utility BattpackClick on Configuration Click on UPS Operating Parameters To see the change in number of external battery packs Racks Rack Type Hole Type Hardware Required Hardware IncludedAppendix C Transporting Your Smart-UPS