American Power Conversion 2200XLT, 5000T, 3000T Determine the Location of the UPS in the Rack

Page 9

Determine the Location of the UPS in the Rack

UPSs are heavy. Select a rack location sturdy enough to handle the weight. Mount the UPS at or near the bottom of the rack.

Select a rack location with adequate air flow that is free from excessive dust. Ensure that any air vents on the sides of the UPS are not blocked. Do not operate the UPS where temperature or humidity are outside the limits listed under Specifications, page 17.

Two additional sets of bracket holes, shown below at asterisks (*), are located on the sides of all rack mount UPS models except the 5000 VA. These holes allow mounting the brackets with a three inch or six inch setback. Move the mounting brackets back if desired to optimize the esthetic or physical requirements of the rack. The 5000 VA unit cannot be mounted in a setback position since it requires the full depth of the rack.

* *

Caution:

Check the rack to make sure it won’t tip after moving the mounting brackets.

1. Determine where in the rack you’ll mount the UPS. The SU5000 requires a space of 5U. Some racks have tick marks to indicate the U-spaces.

2.Using the mounting template provided (part number 990-0195), identify and mark the correct mounting holes for the UPS

 

mounting brackets.

 

3.

Locate and mark the bottom hole in the designated U-space ￿.

 

The bottom screw on the mounting rail will attach to the bottom

￿

hole in the U-space.

 

 

 

4.

Repeat steps 2 and 3 for the remaining three rack posts.

5.

Prepare the rack holes, if necessary. Racks with threaded holes

 

require no preparation.

 

 

If your rack has round holes, insert clip nuts

(provided) into

 

the holes marked in step 2.

 

 

If your rack has square holes, insert either clip

or cage

 

nuts into the holes marked in step 2.

 

1

2

 

￿

￿

Remove the two screws ￿ that hold the rails together so that the rails can slide outward ￿. Do not detach the rails.

Front

Align the bottom hole on the mounting rail with the bottom hole in the U-space (marked in step 3 above). Use the flat, Phillips head screws (10-32) and conical washers to attach the front rail to the rack. Position the rails so that the lip of the rail is on the bottom.

3

990-7031C, Revision 4 12/99

Image 9
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Handling Safety Electrical SafetyReplacement and Recycling of Batteries Page Table of Contents Page How to Unpack the SU 5000 UPS ContentsIntroduction UnpackingInstallation PlacementInstalling Rack Mount Units Determine the Location of the UPS in the Rack Rack Mount Options Load the UPS into the RackTower Units Connect the Batteries5U Rack Mount Units 3U Rack Mount UnitsRear Views Initial StartupConnect Ground Leads to Tvss Connector Optional Charge the batteryBattery Pack Connector Optional Low Battery Warning IntervalOperating Instructions Load Bar Graph Low BatteryOverload SmartTrimStorage Replacing the BatteryStorage Conditions Extended storageBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units How to Determine On-Battery Run Time User Configuration ItemsTypical On-Battery Runtime Versus Load, in Hours Tower and 5U Models 1400VA and 2200VA ModelsLoad VA Internal Battery VA w/ 1 Battery Pack Typical On-Battery Run Time Versus Load, in HoursTower and 5U Rack Mount Models 3000 & 5000 VA Models 3U Rack Mount Models 2200 & 3000 VA Models1400 VA 2200 VA 3000 VA 5000 VA SpecificationsTroubleshooting Limited Warranty ServiceIf the UPS requires service do not return it to the dealer APC Contact InformationAppendix a XL Information XL InstallationSmart-UPS Battery Protocol Use the Smart-UPS Battery Pack Utility BattpackClick on Configuration Click on UPS Operating Parameters To see the change in number of external battery packs Rack Type Hole Type Hardware Required Hardware Included RacksAppendix C Transporting Your Smart-UPS