American Power Conversion 5000T, 2200XLT, 3000T, 1400XLT 3U Rack Mount Units, 5U Rack Mount Units

Page 12

3U Rack Mount Units

1. Reach into the finger pull and open the front cover. Swing the cover open as shown.

2.Unhook the side of the cover from the chassis and lift it away to expose the battery door.

3.Use a flat-blade or Phillips screwdriver or a coin to remove the two battery door screws and

open the door.

4.Connect the battery leads to the battery. Connect the red wire to the positive (+) terminal and the black wire to the negative (–) terminal.

5.Close the battery door, replace the battery compartment screws, and replace the front cover.

5U Rack Mount Units

1.Reach into the finger pull and open the front cover. Swing the cover open as shown.

5000 VA

 

 

For 5000 VA units: Remove the front bezel by grasping the finger clips on the side of the

 

 

bezel and carefully loosening the four (4) snaps. Skip to step 3.

 

2.

Unhook the side of the cover from the chassis and lift it away to expose the battery door.

5000 VA

3.

Use a screwdriver or a coin to remove the two (2) battery door screws and open the door.

5000 VA

4.To connect the battery (or set), press the gray connector into the plug at the top of the battery housing.

Note:

The 5000 VA model has four (4) battery packs that must be installed. Be careful lifting the

batteries - they are heavy. Support the bottom of the batteries as you move them.

5. For 5000 VA units:

Hold the battery pack so that the leads are on the right hand side. Slide the battery pack into the UPS.

Press the gray connector into the plug at the right-hand side of the battery compartment. Tuck the white cord (that serves as a handle for the connector) neatly to the side.

6.For 5000 VA units, repeat step 5 for the remaining three (3) battery packs.

7.Close the battery door, replace the screws, and replace the front cover.

990-7031C, Revision 4 12/99

6

Image 12
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Handling Safety Electrical SafetyReplacement and Recycling of Batteries Page Table of Contents Page Contents How to Unpack the SU 5000 UPSIntroduction UnpackingInstallation PlacementInstalling Rack Mount Units Determine the Location of the UPS in the Rack Load the UPS into the Rack Rack Mount OptionsConnect the Batteries Tower Units3U Rack Mount Units 5U Rack Mount UnitsInitial Startup Rear ViewsCharge the battery Connect Ground Leads to Tvss Connector OptionalBattery Pack Connector Optional Low Battery Warning IntervalOperating Instructions Low Battery Load Bar GraphOverload SmartTrimReplacing the Battery StorageStorage Conditions Extended storageBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units User Configuration Items How to Determine On-Battery Run TimeTypical On-Battery Runtime Versus Load, in Hours Tower and 5U Models 1400VA and 2200VA ModelsTypical On-Battery Run Time Versus Load, in Hours Load VA Internal Battery VA w/ 1 Battery PackTower and 5U Rack Mount Models 3000 & 5000 VA Models 3U Rack Mount Models 2200 & 3000 VA ModelsSpecifications 1400 VA 2200 VA 3000 VA 5000 VATroubleshooting Service Limited WarrantyIf the UPS requires service do not return it to the dealer APC Contact InformationXL Installation Appendix a XL InformationSmart-UPS Battery Protocol Use the Smart-UPS Battery Pack Utility BattpackClick on Configuration Click on UPS Operating Parameters To see the change in number of external battery packs Racks Rack Type Hole Type Hardware Required Hardware IncludedAppendix C Transporting Your Smart-UPS