American Power Conversion 5000T, 2200XLT, 3000T Battery Replacement Procedure 5U Rack Mount Units

Page 20

5000 VA

5000 VA

1400 VA

5000 VA

1400 VA

5000 VA

Battery Replacement Procedure - 5U Rack Mount Units

1.Reach into the finger pull and open the front cover. Swing the cover open as shown.

For 5000 VA units: Remove the front bezel by grasping the finger clips on the side of the bezel and carefully loosening the four (4) snaps. Skip to step 3.

2.Unhook the side of the cover from the chassis and lift it away to expose the battery door.

3.Use a screwdriver or a coin to remove the two (2) battery door screws and open the door.

4.Disconnect the front battery pack:

For the 1400 – 3000 VA models, gently but firmly pull the red and black wires at the top of the battery housing to disconnect the gray connector plug from the UPS.

For the 5000 VA model, grip the white cord on the front set of batteries and pull firmly to disconnect the connector.

5.Pull the front battery out of the UPS by pulling on the clear label, not the white cord. Remove the foam spacer and set it aside. (The 5000 VA unit does not use foam spacers.)

Notes:

Be careful removing the batteries - they are heavy. Support the bottom of the batteries as

you remove them.

The 5000 VA model has four sets of batteries.

6.Reach into the battery compartment and grasp the white cord on the other battery connector. Pull firmly to disconnect the connector and remove the rear set of batteries.

7.Slide the rear set of new batteries into the unit.

For 1400 – 3000 VA units: Hold the connector down below the top of the batteries and toward the door, otherwise the assembly will not fit.

Guide the connector over the top of the batteries and press firmly to connect it to the rear connector of the battery compartment.

For 5000 VA units: Hold the battery pack so that the leads are on the right-hand side. Slide the battery pack into the UPS.

Press the gray connector into the plug at the top of the battery compartment. Tuck the white cord (that serves as a handle for the connector) neatly to the side.

8.Set the foam spacer (if used) against the rear batteries to prevent the wires from being pinched.

9.Slide the front set of batteries in, then guide the connector over the batteries and press firmly to connect it to the front connector of the battery compartment.

Notes:

For the 5000 VA model, repeat steps 4 through 9 for the second set of batteries.

Small sparks at the battery connectors are normal during connection.

10. Close the battery door, replace the screws, and replace the front cover.

Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery’s packing material. See the new battery instructions for more information.

990-7031C, Revision 4 12/99

14

Image 20
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Replacement and Recycling of Batteries Handling SafetyElectrical Safety Page Table of Contents Page Contents How to Unpack the SU 5000 UPSIntroduction UnpackingInstalling Rack Mount Units InstallationPlacement Determine the Location of the UPS in the Rack Load the UPS into the Rack Rack Mount OptionsConnect the Batteries Tower Units3U Rack Mount Units 5U Rack Mount UnitsInitial Startup Rear ViewsCharge the battery Connect Ground Leads to Tvss Connector OptionalBattery Pack Connector Optional Low Battery Warning IntervalOperating Instructions Low Battery Load Bar GraphOverload SmartTrimReplacing the Battery StorageStorage Conditions Extended storageBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units User Configuration Items How to Determine On-Battery Run TimeTypical On-Battery Runtime Versus Load, in Hours Tower and 5U Models 1400VA and 2200VA ModelsTypical On-Battery Run Time Versus Load, in Hours Load VA Internal Battery VA w/ 1 Battery PackTower and 5U Rack Mount Models 3000 & 5000 VA Models 3U Rack Mount Models 2200 & 3000 VA ModelsSpecifications 1400 VA 2200 VA 3000 VA 5000 VATroubleshooting Service Limited WarrantyIf the UPS requires service do not return it to the dealer APC Contact InformationXL Installation Appendix a XL InformationClick on Configuration Click on UPS Operating Parameters Smart-UPS Battery ProtocolUse the Smart-UPS Battery Pack Utility Battpack To see the change in number of external battery packs Racks Rack Type Hole Type Hardware Required Hardware IncludedAppendix C Transporting Your Smart-UPS