American Power Conversion 1400XLT, 5000T, 3000T Battery Replacement Procedure 3U Rack Mount Units

Page 19

Battery Replacement Procedure - 3U Rack Mount Units

1.Reach into the finger pull and open the front cover. Swing the cover open as shown.

2.Unhook the side of the cover from the chassis and lift it away to expose the battery door.

3.Use a flat-blade or Phillips screwdriver or a coin to remove the two battery door screws and open the door.

4.Grasp the tab and gently pull the battery out of the UPS.

5.Disconnect the battery leads. Loosen the connectors by gently wiggling them while pulling straight back from the battery connector.

6.Connect the battery leads to the new battery. Connect the red wire to the positive (+) terminal and the black wire to the negative (–) terminal.

7.Slide the battery into the UPS.

8.Close the battery door, replace the battery compartment screws, and replace the front cover.

Notes:

Be careful removing the batteries - they are heavy.

Small sparks at the battery connectors are normal during connection.

Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery’s packing material. See the new battery instructions for more information.

13

990-7031C, Revision 4 12/99

Image 19
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Electrical Safety Handling SafetyReplacement and Recycling of Batteries Page Table of Contents Page Unpacking ContentsHow to Unpack the SU 5000 UPS IntroductionPlacement InstallationInstalling Rack Mount Units Determine the Location of the UPS in the Rack Rack Mount Options Load the UPS into the RackTower Units Connect the Batteries5U Rack Mount Units 3U Rack Mount UnitsRear Views Initial StartupLow Battery Warning Interval Charge the batteryConnect Ground Leads to Tvss Connector Optional Battery Pack Connector OptionalOperating Instructions SmartTrim Low BatteryLoad Bar Graph OverloadExtended storage Replacing the BatteryStorage Storage ConditionsBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units Tower and 5U Models 1400VA and 2200VA Models User Configuration ItemsHow to Determine On-Battery Run Time Typical On-Battery Runtime Versus Load, in Hours3U Rack Mount Models 2200 & 3000 VA Models Typical On-Battery Run Time Versus Load, in HoursLoad VA Internal Battery VA w/ 1 Battery Pack Tower and 5U Rack Mount Models 3000 & 5000 VA Models1400 VA 2200 VA 3000 VA 5000 VA SpecificationsTroubleshooting APC Contact Information ServiceLimited Warranty If the UPS requires service do not return it to the dealerAppendix a XL Information XL InstallationUse the Smart-UPS Battery Pack Utility Battpack Smart-UPS Battery ProtocolClick on Configuration Click on UPS Operating Parameters To see the change in number of external battery packs Rack Type Hole Type Hardware Required Hardware Included RacksAppendix C Transporting Your Smart-UPS