American Power Conversion 1400XLT, 5000T, 2200XLT Specifications, 1400 VA 2200 VA 3000 VA 5000 VA

Page 23

Specifications

 

1400 VA

 

2200 VA

 

3000 VA

 

5000 VA

Acceptable input voltage

 

 

0 - 325 VAC

 

Input voltage (on-line operation)*

 

160 - 253

VAC

 

208 volt output range*

 

 

177 - 229 VAC

 

120 volt output range *

 

 

 

 

 

 

 

 

with 400 VA load

 

 

95 - 130 VAC

 

with no load

 

 

100 - 135 VAC

 

Nominal input frequency

 

 

50 or 60 Hz, autosensing

 

Input protection

 

 

Resettable circuit breaker

 

Frequency limits (on-line operation)

 

 

47 to 63 Hz

 

Transfer time

 

 

2 ms typical, 4.5 ms maximum

 

Maximum load, total

1400 VA/950 W

 

2200 VA/1600 W

3000 VA/2250 W

 

5000 VA/3750 W

Maximum load, 120V auxiliary

 

 

400 VA/400 W

 

On-battery output voltage

 

 

208 VAC

 

On-battery frequency

 

 

50 or 60 Hz,

0.1 Hz;

 

 

 

unless synchronized to utility during brownout

 

On-battery waveshape

 

 

Low-distortion sine wave

 

Overload protection (on-battery)

Overcurrent and short-circuit protected, latching shutdown on overload

Overload protection (on-line)

 

2 pole, 20 Amp UL certified input circuit breaker

 

Overload protection

 

Transformer and output protected by resettable

 

(120 VAC auxiliary)

 

thermal circuit breaker (on-line and on-battery)

 

Surge energy rating

 

 

 

 

 

 

 

 

(one time, 10/1000 æs waveform)

 

 

1120 J

 

Surge current capability

 

 

 

 

 

 

 

 

(one time, 8/20 æs waveform)

 

 

6500 A maximum

 

Surge response time

 

 

0 ns (instantaneous) normal mode;

 

 

 

 

z5 ns common mode

 

Surge voltage let-through

 

 

 

 

 

 

 

 

(percentage of applied ANSI C62.41 Cat. A

 

0.30%

 

 

6 kV test waveform)

 

 

 

 

 

 

 

 

Noise filter

 

Normal and common mode EMI/RFI suppression,

 

 

 

 

100 kHz to 10 MHz

 

Battery type

 

Spill proof, maintenance free, sealed lead-acid

 

Typical battery life

3 to 6 years, depending on number of discharge cycles

 

 

 

and ambient temperature

 

Typical recharge time

 

 

2 to 5 hours from total discharge

 

Operating temperature

 

 

0 to 40ΓC (+32 to +104ΓF)

 

Storage temperature

 

 

-15 to +45ΓC (+5 to +113ΓF)

 

Operating and storage relative humidity

 

 

5 to 95%, non-condensing

 

Operating elevation

 

 

0 to +3,000 m (0 to +10,000 ft.)

 

Storage elevation

 

 

0 to +15,000 m (0 to +50,000 ft.)

 

Electromagnetic immunity

 

IEC 801-2 level IV, 801-3 level III, 801-4 level IV

Audible noise in dBA at 1 m (3 ft.)

 

 

z55

 

 

 

Safety approvals

 

 

Listed to UL 1778, certified to CSA 107.1

 

EMI verification

 

 

FCC/DOC Class A verified

 

 

 

 

5U Units

 

 

RM Units

Size (W x H x D)

 

43.2 x 19.6 x 54.6 cm

 

43.2 x 19.6 x 62.2 cm

 

 

(17.0 x 8.7 x 21.5 in.)

 

(17.0 x 8.7 x 24.5 in.)

Weight - net (shipping)

120 (143) lb.

 

137 (160) lb.

 

137 (160) lb.

 

225 (245) lb.

 

54.3 (64.8) kg

 

62.0 (72.5) kg

 

62.0 (72.5) kg

 

102 (111) kg

 

 

 

3U Units

 

 

Tower Units

Size (W x H x D)

 

43.2 x 13.3 x 62.2 cm

 

19.6 x 43.2 x 62.2 cm

 

 

(17.0 x 5.25 x 24.5 in.)

 

(8.7 x 17.5 x 26.0 in.)

Weight - net (shipping)

 

 

128 (148) lb.

 

 

230 (250) lb.

 

 

 

58 (67) kg

 

 

105 (114) kg

17

990-7031C, Revision 4 12/99

Image 23
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Replacement and Recycling of Batteries Handling SafetyElectrical Safety Page Table of Contents Page Unpacking ContentsHow to Unpack the SU 5000 UPS IntroductionInstalling Rack Mount Units InstallationPlacement Determine the Location of the UPS in the Rack Rack Mount Options Load the UPS into the RackTower Units Connect the Batteries5U Rack Mount Units 3U Rack Mount UnitsRear Views Initial StartupLow Battery Warning Interval Charge the batteryConnect Ground Leads to Tvss Connector Optional Battery Pack Connector OptionalOperating Instructions SmartTrim Low BatteryLoad Bar Graph OverloadExtended storage Replacing the BatteryStorage Storage ConditionsBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units Tower and 5U Models 1400VA and 2200VA Models User Configuration ItemsHow to Determine On-Battery Run Time Typical On-Battery Runtime Versus Load, in Hours3U Rack Mount Models 2200 & 3000 VA Models Typical On-Battery Run Time Versus Load, in HoursLoad VA Internal Battery VA w/ 1 Battery Pack Tower and 5U Rack Mount Models 3000 & 5000 VA Models1400 VA 2200 VA 3000 VA 5000 VA SpecificationsTroubleshooting APC Contact Information ServiceLimited Warranty If the UPS requires service do not return it to the dealerAppendix a XL Information XL InstallationClick on Configuration Click on UPS Operating Parameters Smart-UPS Battery ProtocolUse the Smart-UPS Battery Pack Utility Battpack To see the change in number of external battery packs Rack Type Hole Type Hardware Required Hardware Included RacksAppendix C Transporting Your Smart-UPS