Smart-UPS Battery Protocol

Smart-UPS XL models are not designed to know how many external battery packs are connected to them. You must program the Smart-UPS XL with the appropriate number of external batteries in one of four ways.

Note:

It is important to follow these instructions. The number of batteries affects the run time calculations which

Smart-UPS performs when it is running on battery power.

Use the Smart-UPS Battery Pack Utility (BATTPACK)

This program can be used with DOS or at a Microsoft® Windows DOS prompt.

BATTPACK cannot be used with a DOS emulator or VDM (virtual DOS machine) like those in Windows 95, Windows 98, or Windows NT.

The APC UPS Link cable must be used to communicate to the UPS. There are two black cables which can be used; part numbers 940-0024C or 940-1524C.

Note:

For the purposes of this formula, 1 rack mount battery pack (SU48RMXLBP) = 2 stand-alone battery packs.

At the DOS prompt, type: battpack com[X] [Y] where:

[X]represents the available serial port that Battery Pack Utility uses to access the Smart-UPS.

[Y]represents the number of external battery packs.

For example: C:> battpack com1 4

The black cable is attached to communication port 1. There are four external battery packs. The program confirms that the update is successful.

Use PowerChute® plus Version 5.x for Windows 95, Windows 98, Windows NT

PowerChute plus 5.x for Windows NT is compatible with NT 3.5.1 SP5, NT 4.0 Workstation (at least SP1), or NT 4.0 Server (at least SP1).

Install the software per the instructions on the CD.

After rebooting the computer, access the PowerChute plus graphical user interface.

1.Click on Configuration.

2.Click on UPS Operating Parameters.

3.Adjust the External Battery Pack field to the appropriate number of external batteries.

4.Click OK.

Use the Terminal Program to Change the Number of External Battery Packs

Terminal is used in Windows 3.1x, Windows for Workgroups, and Windows NT 3.51.

1.EXIT out of the PowerChute plus Server. In the case of Windows NT, the UPS Service must be stopped.

2.Go to: Program Manager > Accessories > Terminal. Double-click on the Terminal icon.

3.Select the COM port to which the black-colored interface cable is attached as the Connector.

4.The COM port settings are 2400 baud, 8 data bits, 1 stop bit, no parity, flow control is Xon/Xoff.

5.Click OK.

6.Continue with the table in Step 7 in Use the HyperTerminal Program to Change the Number of External Battery Packs, page 22.

21

990-7031C, Revision 4 12/99

Image 27
Contents 990-7031C, Revision 4 12/99 990-7031C, Revision 4 12/99 Handling Safety Electrical SafetyReplacement and Recycling of Batteries Page Table of Contents Page Unpacking ContentsHow to Unpack the SU 5000 UPS IntroductionInstallation PlacementInstalling Rack Mount Units Determine the Location of the UPS in the Rack Rack Mount Options Load the UPS into the RackTower Units Connect the Batteries5U Rack Mount Units 3U Rack Mount UnitsRear Views Initial StartupLow Battery Warning Interval Charge the batteryConnect Ground Leads to Tvss Connector Optional Battery Pack Connector OptionalOperating Instructions SmartTrim Low BatteryLoad Bar Graph OverloadExtended storage Replacing the BatteryStorage Storage ConditionsBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units Tower and 5U Models 1400VA and 2200VA Models User Configuration ItemsHow to Determine On-Battery Run Time Typical On-Battery Runtime Versus Load, in Hours3U Rack Mount Models 2200 & 3000 VA Models Typical On-Battery Run Time Versus Load, in HoursLoad VA Internal Battery VA w/ 1 Battery Pack Tower and 5U Rack Mount Models 3000 & 5000 VA Models1400 VA 2200 VA 3000 VA 5000 VA SpecificationsTroubleshooting APC Contact Information ServiceLimited Warranty If the UPS requires service do not return it to the dealerAppendix a XL Information XL InstallationSmart-UPS Battery Protocol Use the Smart-UPS Battery Pack Utility BattpackClick on Configuration Click on UPS Operating Parameters To see the change in number of external battery packs Rack Type Hole Type Hardware Required Hardware Included RacksAppendix C Transporting Your Smart-UPS