9 Storage/Operating Environment

Observe the following when storing the UPS.

Store UPS indoors.

Maximum storage time for the UPS between powered operation cycles is three years. If the UPS has been stored for a period exceeding 36 months, contact your factory authorized represnetative of guidance in starting the unit.

Temperature fluctuations should be minimized.

The optimal storage temperature range is 68 – 77 °F (20 – 25° C).

A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.

The optimal relative humidity at the storage location should be between 50 – 60%.

Humidity must not exceed 90%.

Avoid locations where UPS may be exposed to corrosive gas.

Avoid locations with dirt and/or dust.

TABLE 9.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS

Item

Environment standard

 

Storage Location

Indoors

 

Ambient Temperature

Minimum storage temperature: 32 °F (0 °C)

Maximum storage temperature: 104 °F (40 °C)

 

Relative Humidity

The relative humidity must be between 30 and 90% and without condensation

due to temperature changes.

 

 

 

 

This equipment is rated for installations up to 3240 ft. (1000m) above

Altitude

sea level. Consult with the factory to determine the derating factor for

 

installations above 3240 ft. (1000m).

Dust

Dust must not exceed normal atmospheric levels and must not include

conductive particles, silicone or oils.

 

 

No flammable and/or explosive gas.

 

Hydrogen sulfide (H2S)

Less than or equal to 0.0001 PPM

 

Sulfurous acid gas (SO2)

Less than or equal to 0.05 PPM

 

Chlorine gas (Cl2)

Less than or equal to 0.002 PPM

Flammable Gas

 

 

Ammonia gas (NH3)

Less than or equal to 0.1 PPM

 

Nitrous acid gas (NO2)

Less than or equal to 0.02 PPM

 

Nitrous oxides (NOx)

Less than or equal to 0.02 PPM

 

Ozone (O3)

Less than or equal to 0.002 PPM

 

Hydrochloric acid mist (HCl)

Less than or equal to 0.1 mg/m3

9.1Operating Precautions

Initial startup/comisioning of the UPS should be performed by factory authorized personnel.

1)The UPS should not be powered up until the entire operation manual has been read.

2)The voltage of the input power source must be within the rated input voltage range. The input frequency range must be within the rated input frequency range.

22

G8000 Series Installation and Operation Manual

Image 30
Contents G8000 Series Page Document July Qualified Personnel only Uninterruptible Power System UPS Toshiba Customer Support Center PurposeToshiba’s Customer Support Center Toshiba International CorporationTable of Contents 11.4 Introduction General Safety Instructions SymbolsProhibited Symbol indicates do not take action Signal Words Qualified PersonnelImportant Safety Instructions Factory Authorized PersonnelSafety Precautions DisclaimerTransporting/Unpacking General MaintenanceKeep the area arround the UPS clean Do not tilt the UPS more than 10 from upright positionDo not transport, move, store, or place the UPS on its side Avoid vibration or shock exceeding 0.5GInspection/Storage Installation Precautions Install the UPS in a controlled environmentKeep the Specified Clearance around the UPS Do not install the UPS where water may fall on it Do not block air ventsInstallation Precautions Environment standardMetal Conduit is not AN Acceptable Ground Conductor Routing and GroundingConnect only one 1 ground wire to the earth ground terminal Wiring/ConnectionPerform wiring and connections with correct polarity Follow the torque criteria for tightening screwsFor 100, 150, 225KVA GND 150/225 KVA UPS Warning Labels Weight and Dimensions Model Unit Shipping300 KVA UPS Exterior Dimensions Inches Transporting Transporting By Crane 8.5 show examples of acceptable and unacceptable operationsTransporting By Forklift Transporting UPS by ForkliftOperating Precautions Storage/Operating EnvironmentPage Maintenance Precautions Qualified Personnel onlyQualified Personnel shall Disposal Do not dispose of the batteries in a fireDo not open or mutilate the batteries Installation Unpacking UPS ClearanceAnchor Bolt Installation Detail Anchor BoltsUPS Wiring External Wiring Diagram11.1 100 kVA Terminal Blocks and Power Cables Block Number Cable Size Tightening TorqueAC Input Bypass Input AC Output Battery YA36L Block Number Cable Size Recommended Fastener TorqueBus Number Cable Size Recommended Fastener Torque UPS Power Cable Knockout Plates Bottom Cable Knockout Plates for 100 KVA T80S3K10KK6XS2HPlate #2 Plate #3 Terminal Knockout Plates for the 300 KVA UPSGrounding Wire External BreakersBe sure to ground the UPS as specified G8000 100 kVA G8000 150/225 kVA Control Wires Signal Name Operation11 Connection Between UPS, Battery Cabinet & Bypass Breaker Grounding Configuration 12 Grounding Configuration with Input Neutral GroundedGrounding Configuration without input neutral Recommended Configuration for delta-inputGrounding Configuration with corner-grounded delta-input 16 Grounding Configuration with CORNER-GROUNDED DELTA-INPUTMechanical Specification UPS SpecificationsGeneral Specification Terms Specification RemarksNominal Capacity 150 kW 225 kW 300 kW Electrical Specification Do not open the front coverOperator Interface UPS may not respond if the button press is too shortKey-Switch and Buttons Graphic Display Panel KEY-SWITCH/OPERATING Buttons13.2 LCD/LED Indicators Graphic Display Panel LCD/LED IndicatorsLCD Indicators Name DescriptionVolt Freq .0Hz Normal DisplayAC-VO AC- I O 50% 50%DC-V BATT-V BATT- I 0A AC I/P-V Freq .0HzBYP I/P-V Freq .0Hz 32TIMFault Display 09-09-06LCD Scroll AbbreveationsEPO and Control Power Supply Operating Switches Operating the UPSOperation Types Pre-operational CheckPerform the pre-operational check before operating the UPS Startup Procedures Procedure to start the UPS is shown in StepsAC Vo 480 AC Io 50% Switch Power Supply UPS→Bypass Bypass LED is onStop Complete Shutdown DC-V 0 BATT-V 0 BATT-I 0 aChanging Between Float Charge and Equalize Charge Make sure that the Float Charge LED is onMake sure that the Equal Charge LED is on Troubleshooting Emergency Power Off EPOTypes of Errors Faults and Warnings Data Screen 09-09-06LCD Fault & Warning Displays Fault DisplayFault Messages LCD Message Indication DescriptionLCD Message Indication Description LCD Scroll w/ faults or warnings ResetDo not attempt to modify or relocate the UPS Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not open the front and/or rear panelsPage Page Industrial Division