Toshiba 300 KW operation manual Nominal Capacity 150 kW 225 kW 300 kW

Page 52

12.2Mechanical Specification (cont.)

Nominal Capacity

150 kW

 

225 kW

300 kW

Cabinet Protection

 

 

IEC298 IP20*

 

Conformity

 

 

 

 

 

 

 

Exterior Paint

Sherwin Williams, HHT2-7055, 079 Beige Texture

 

 

 

FRONT: 1/16 in. (1.6 mm)

Panel Thickness

BACK/SIDE/TOP: 3/64 in. (1.2 mm)

 

 

 

BOTTOM: 1/8 in. (3.2 mm)

Input/Output

TOP and BOTTOM

TOP

Cabling Entrance

 

 

 

 

Ground/Control

TOP and BOTTOM

TOP

Wiring Entrance

 

 

 

 

 

W: 55.1 in. (1400 mm)

W: 76.8 in. (1951 mm)

Outline Dimension

D: 31.8 in. (808 mm)

D: 31.8 in. (808 mm)

 

H: 79.2 in. (2012 mm)

H: 79.4 in. (2017 mm)

Unit Weight

2467 lbs (1119 kg)

 

2980 lbs (1352 kg)

4575 lbs (2075 kg)

Shipping Weight

2556 lbs (1159 kg)

 

3069 lbs (1392 kg)

4725 lbs (2143 kg)

Floor Loading Per

3280 lbs/ft2

 

3733 lbs/ft2

2460 lbs/ft2

Footprint

(16,014 kg/m2)

 

(18,226 kg/m2)

(12,011 kg/m2)

 

 

FRONT: 43 7/16 in. (1100 mm)

Clearance

 

 

BACK/SIDE: 0 in. (0 mm)

 

 

 

TOP: 15 3/4 in. (400 mm)

Heat Rejection

51,182 BTU/h

 

68,243 BTU/h

68,243 BTU/h

(12,897 kcal/h)

 

(17,197 kcal/h)

(17,197 kcal/h)

 

 

*IP20: Foreign objects that are 12 mm (15/32 in.) or larger are prevented from entering the enclosure of the UPS.

44

G8000 Series Installation and Operation Manual

Image 52
Contents G8000 Series Page Document July Qualified Personnel only Uninterruptible Power System UPS Purpose Toshiba’s Customer Support CenterToshiba Customer Support Center Toshiba International CorporationTable of Contents 11.4 Introduction Symbols General Safety InstructionsProhibited Symbol indicates do not take action Signal Words Qualified PersonnelImportant Safety Instructions Factory Authorized PersonnelSafety Precautions DisclaimerGeneral Maintenance Keep the area arround the UPS cleanTransporting/Unpacking Do not tilt the UPS more than 10 from upright positionDo not transport, move, store, or place the UPS on its side Avoid vibration or shock exceeding 0.5GInspection/Storage Install the UPS in a controlled environment Installation PrecautionsKeep the Specified Clearance around the UPS Do not install the UPS where water may fall on it Do not block air ventsInstallation Precautions Environment standardMetal Conduit is not AN Acceptable Ground Conductor Routing and GroundingWiring/Connection Perform wiring and connections with correct polarityConnect only one 1 ground wire to the earth ground terminal Follow the torque criteria for tightening screwsFor 100, 150, 225KVA GND 150/225 KVA UPS Warning Labels Weight and Dimensions Model Unit Shipping300 KVA UPS Exterior Dimensions Inches Transporting Transporting By Crane 8.5 show examples of acceptable and unacceptable operationsTransporting By Forklift Transporting UPS by ForkliftOperating Precautions Storage/Operating EnvironmentPage Qualified Personnel only Maintenance PrecautionsQualified Personnel shall Do not dispose of the batteries in a fire DisposalDo not open or mutilate the batteries Installation Unpacking UPS ClearanceAnchor Bolt Installation Detail Anchor BoltsUPS Wiring External Wiring Diagram11.1 100 kVA Terminal Blocks and Power Cables Block Number Cable Size Tightening TorqueAC Input Bypass Input AC Output Battery YA36L Block Number Cable Size Recommended Fastener TorqueBus Number Cable Size Recommended Fastener Torque UPS Power Cable Knockout Plates Bottom Cable Knockout Plates for 100 KVA T80S3K10KK6XS2HPlate #2 Plate #3 Terminal Knockout Plates for the 300 KVA UPSExternal Breakers Grounding WireBe sure to ground the UPS as specified G8000 100 kVA G8000 150/225 kVA Control Wires Signal Name Operation11 Connection Between UPS, Battery Cabinet & Bypass Breaker Grounding Configuration 12 Grounding Configuration with Input Neutral Grounded Grounding Configuration without input neutral Recommended Configuration for delta-inputGrounding Configuration with corner-grounded delta-input 16 Grounding Configuration with CORNER-GROUNDED DELTA-INPUTUPS Specifications General SpecificationMechanical Specification Terms Specification RemarksNominal Capacity 150 kW 225 kW 300 kW Electrical Specification Do not open the front coverOperator Interface UPS may not respond if the button press is too shortKey-Switch and Buttons Graphic Display Panel KEY-SWITCH/OPERATING Buttons13.2 LCD/LED Indicators Graphic Display Panel LCD/LED IndicatorsLCD Indicators Name DescriptionNormal Display AC-VO AC- I O 50%Volt Freq .0Hz 50%AC I/P-V Freq .0Hz BYP I/P-V Freq .0HzDC-V BATT-V BATT- I 0A 32TIMFault Display 09-09-06LCD Scroll AbbreveationsEPO and Control Power Supply Operating Switches Operating the UPSPre-operational Check Operation TypesPerform the pre-operational check before operating the UPS Startup Procedures Procedure to start the UPS is shown in StepsAC Vo 480 AC Io 50% Switch Power Supply UPS→Bypass Bypass LED is onStop Complete Shutdown DC-V 0 BATT-V 0 BATT-I 0 aChanging Between Float Charge and Equalize Charge Make sure that the Float Charge LED is onMake sure that the Equal Charge LED is on Emergency Power Off EPO TroubleshootingTypes of Errors Faults and Warnings Data Screen 09-09-06LCD Fault & Warning Displays Fault DisplayFault Messages LCD Message Indication DescriptionLCD Message Indication Description LCD Scroll w/ faults or warnings ResetContact Toshiba in the event of malfunction or fault Restoring UPS OperationDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsPage Page Industrial Division