12.3Electrical Specification
WARNING
DO NOT open the front cover.
Electric shock, burns or other personal injuries may occur if untrained personnel open the front cover.
Nominal Capacity | 100 kW | 150 kW | 225 kW | 300 kW |
AC Input Rated Capacity* | 110 kW (120 kW) | 165 kW (180 kW) | 245 kW (270 kW) | 320 kW (320 kW) |
Input Voltage |
| 480 V ( +10% to |
| |
Input Frequency |
| 60 Hz ±5% |
| |
Input Power Factor |
| 0.95 – 1.00 Lagging ( at 100% Load ) |
| |
Current Harmonic Distortion |
| 4% Maximum ( at 100% Load ) |
| |
Input Capacity Required* | 111 kVA (124 kVA) | 166 kVA (184 kVA) | 250 kVA (274 kVA) | 327 kVA (332 kVA) |
Circuit Breaker Rating At 480 V | 200 A Trip | 300 A Trip | 450 A Trip | 500 A Trip |
Input |
|
|
|
|
| * Capacity: Normal Mode (Recharge Mode) |
|
Nominal Capacity | 100 kW | 150 kW | 225 kW | 300 kW |
DC Input Voltage Window |
| 288 – 414 VDC |
| |
Recharge Voltage Regulation |
| ± 1.5% |
| |
|
|
|
|
|
Nominal Capacity | 100 kW | 150 kW | 225 kW | 300 kW |
AC Output Rated Capacity* | 100 kVA (100 kW) | 150 kVA (150 kW) | 225 kVA (225 kW) | 300 kVA (300 kW) |
Output Voltage |
| 480/277 V ± 1%, |
| |
Output Power Factor |
| 1.0 PF: 32 – 86 °F (0 – 30 °C) |
| |
|
| 0.8 PF: 86 – 104 °F (30 – 40 °C) |
| |
Voltage Distortion | 3% with 100% Linear Load / 5% with | |||
Transient Voltage Regulation |
| < ± 2% |
| |
Transient Settling Time |
| < 50 ms |
| |
Crest Factor |
| 2.0 |
| |
Output Frequency |
| 60 Hz ± 0.01% ( at |
| |
Synchronous Window To Utility Line |
| 59 Hz – 61 Hz |
| |
Frequency Slew Rate |
| 1 Hz/Sec |
| |
Over Load Rating | 100% – Continuous / 125% – 10 min. / 150% – 1 min. |
* Capacity: Normal Mode (Recharge Mode)
G8000 Series Installation and Operation Manual | 45 |