Toshiba 300 KW operation manual Control Wires, Signal Name Operation

Page 46

11.6Control Wires

The control wires terminal layouts at TB1 (terminal bus 1) are shown below in Table 11.8.

 

 

 

 

 

TABLE 11.8 EXTERNAL CONNECTIONS

No.

 

I/O

 

 

Signal Name

 

Operation

1

 

Output

 

 

Low Battery

 

Closed at Low Battery

2

 

Output

 

 

Backup Operation

 

Closed during Backup Operation

3

 

Output

 

 

Fault

 

Closed if Faults present

4

 

Output

 

 

Inverter Supply

 

Closed during Normal Operation

5

 

Output

 

 

Warning

 

Closed if Warnings present

6

 

Input

}

 

P24

 

 

7

 

Input

 

Remote Run

 

Close to run UPS

 

 

 

8

 

Input

}

 

P24

 

 

9

 

Input

 

Remote Stop

 

Close to stop UPS

 

 

 

10

 

Output

 

 

Bypass Supply

 

Close during Bypass Operation

11

 

Output

 

 

Output Signal Ground

 

(Ground for pin #1 – 5 & #10)

12

 

Input

}

 

P24

 

Battery’s

13

 

Input

 

Battery Overheat

 

Overheat B-contact

 

 

 

14

 

Output

}

 

 

 

Bypass Breaker

15

 

Output

 

52C Trip Signal

 

Shunt Trip Signal by EPO

 

 

 

16

 

Output

}

 

 

 

Battery Breaker shunt trip

17

 

Output

 

72B Trip Signal

 

by EPO or Battery shutdown

 

 

 

18

 

Output

}

 

 

 

Battery breaker’s

19

 

Output

 

72B Aux. Contact

 

Auxiliary A-contact

 

 

 

20

 

 

 

 

 

 

 

21

 

Output

}

 

External EPO

 

Ext EPO (Customer) N.O. Contacts

22

 

Output

 

External EPO

 

Ext EPO (Customer) N.O. Contacts

 

 

 

Note: All control wiring should be #18 AWG (0.823 mm2) or larger.

38

G8000 Series Installation and Operation Manual

Image 46
Contents G8000 Series Page Document July Qualified Personnel only Uninterruptible Power System UPS Toshiba Customer Support Center PurposeToshiba’s Customer Support Center Toshiba International CorporationTable of Contents 11.4 Introduction Symbols General Safety InstructionsProhibited Symbol indicates do not take action Signal Words Qualified PersonnelImportant Safety Instructions Factory Authorized PersonnelSafety Precautions DisclaimerTransporting/Unpacking General MaintenanceKeep the area arround the UPS clean Do not tilt the UPS more than 10 from upright positionDo not transport, move, store, or place the UPS on its side Avoid vibration or shock exceeding 0.5GInspection/Storage Install the UPS in a controlled environment Installation PrecautionsKeep the Specified Clearance around the UPS Do not install the UPS where water may fall on it Do not block air ventsInstallation Precautions Environment standardMetal Conduit is not AN Acceptable Ground Conductor Routing and GroundingConnect only one 1 ground wire to the earth ground terminal Wiring/ConnectionPerform wiring and connections with correct polarity Follow the torque criteria for tightening screwsFor 100, 150, 225KVA GND 150/225 KVA UPS Warning Labels Weight and Dimensions Model Unit Shipping300 KVA UPS Exterior Dimensions Inches Transporting Transporting By Crane 8.5 show examples of acceptable and unacceptable operationsTransporting By Forklift Transporting UPS by ForkliftOperating Precautions Storage/Operating EnvironmentPage Qualified Personnel only Maintenance PrecautionsQualified Personnel shall Do not dispose of the batteries in a fire DisposalDo not open or mutilate the batteries Installation Unpacking UPS ClearanceAnchor Bolt Installation Detail Anchor BoltsUPS Wiring External Wiring Diagram11.1 100 kVA Terminal Blocks and Power Cables Block Number Cable Size Tightening TorqueAC Input Bypass Input AC Output Battery YA36L Block Number Cable Size Recommended Fastener TorqueBus Number Cable Size Recommended Fastener Torque UPS Power Cable Knockout Plates Bottom Cable Knockout Plates for 100 KVA T80S3K10KK6XS2H Plate #2 Plate #3 Terminal Knockout Plates for the 300 KVA UPSExternal Breakers Grounding WireBe sure to ground the UPS as specified G8000 100 kVA G8000 150/225 kVA Control Wires Signal Name Operation11 Connection Between UPS, Battery Cabinet & Bypass Breaker Grounding Configuration 12 Grounding Configuration with Input Neutral GroundedGrounding Configuration without input neutral Recommended Configuration for delta-inputGrounding Configuration with corner-grounded delta-input 16 Grounding Configuration with CORNER-GROUNDED DELTA-INPUTMechanical Specification UPS SpecificationsGeneral Specification Terms Specification RemarksNominal Capacity 150 kW 225 kW 300 kW Electrical Specification Do not open the front coverOperator Interface UPS may not respond if the button press is too shortKey-Switch and Buttons Graphic Display Panel KEY-SWITCH/OPERATING Buttons13.2 LCD/LED Indicators Graphic Display Panel LCD/LED IndicatorsLCD Indicators Name DescriptionVolt Freq .0Hz Normal DisplayAC-VO AC- I O 50% 50%DC-V BATT-V BATT- I 0A AC I/P-V Freq .0HzBYP I/P-V Freq .0Hz 32TIMFault Display 09-09-06LCD Scroll AbbreveationsEPO and Control Power Supply Operating Switches Operating the UPSPre-operational Check Operation TypesPerform the pre-operational check before operating the UPS Startup Procedures Procedure to start the UPS is shown in StepsAC Vo 480 AC Io 50% Switch Power Supply UPS→Bypass Bypass LED is onStop Complete Shutdown DC-V 0 BATT-V 0 BATT-I 0 aChanging Between Float Charge and Equalize Charge Make sure that the Float Charge LED is onMake sure that the Equal Charge LED is on Emergency Power Off EPO TroubleshootingTypes of Errors Faults and Warnings Data Screen 09-09-06LCD Fault & Warning Displays Fault DisplayFault Messages LCD Message Indication DescriptionLCD Message Indication Description LCD Scroll w/ faults or warnings ResetDo not attempt to modify or relocate the UPS Contact Toshiba in the event of malfunction or faultRestoring UPS Operation Do not open the front and/or rear panelsPage Page Industrial Division