Toshiba 300 KW operation manual Grounding Configuration with Input Neutral Grounded

Page 48

11.7Grounding Configuration

This section describes the grounding configuration to be used with various AC service entrance configurations.

Inadequate grounding will cause problems at start-up. Connections for the ground line and the neutral line must be made appropriately according to the system configuration.

11.7.1Recommended configuration (for 4 wire input with Input Neutral grounded)

Figure 11.12 shows recommended grounding configuration when the input neutral is grounded.

The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should be disconnected from the ground bus. The neutral connection for the UPS bypass input should be grounded.

Input Source

< UPS Cabinet >

 

3φ 3φ

N

N

3φ 3φ

GG

3φ

3φ

 

N

N

To the

G

G

Load

 

Remove

Jumper Cable

FIGURE 11.12 - GROUNDING CONFIGURATION WITH INPUT NEUTRAL GROUNDED

A 2 AWG (or 38 mm2) jumper cable is provided between the neutral terminal and ground bus in the UPS cabinet. The qualified personnel should remove the jumper cable in this configuration. The jumper cable location is illustrated below.

100-225 kVA

 

 

 

 

 

300 kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

 

 

 

 

Ground

Ground

Terminal

 

 

 

 

Bus

Bus

 

 

 

 

Remove

 

 

 

 

 

 

 

 

 

 

Jumper

 

 

 

 

 

 

 

 

 

 

 

 

Cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral

Terminal

Remove

Jumper

Cable

FIGURE 11.13 - JUMPER CABLE BETWEEN THE NEUTRAL TERMINAL & GROUND BUS

40

G8000 Series Installation and Operation Manual

Image 48
Contents G8000 Series Page Document July Qualified Personnel only Uninterruptible Power System UPS Purpose Toshiba’s Customer Support CenterToshiba Customer Support Center Toshiba International CorporationTable of Contents 11.4 Introduction General Safety Instructions SymbolsProhibited Symbol indicates do not take action Signal Words Qualified PersonnelImportant Safety Instructions Factory Authorized PersonnelSafety Precautions DisclaimerGeneral Maintenance Keep the area arround the UPS cleanTransporting/Unpacking Do not tilt the UPS more than 10 from upright positionDo not transport, move, store, or place the UPS on its side Avoid vibration or shock exceeding 0.5GInspection/Storage Installation Precautions Install the UPS in a controlled environmentKeep the Specified Clearance around the UPS Do not install the UPS where water may fall on it Do not block air ventsInstallation Precautions Environment standardMetal Conduit is not AN Acceptable Ground Conductor Routing and GroundingWiring/Connection Perform wiring and connections with correct polarityConnect only one 1 ground wire to the earth ground terminal Follow the torque criteria for tightening screwsFor 100, 150, 225KVA GND 150/225 KVA UPS Warning Labels Weight and Dimensions Model Unit Shipping300 KVA UPS Exterior Dimensions Inches Transporting Transporting By Crane 8.5 show examples of acceptable and unacceptable operationsTransporting By Forklift Transporting UPS by ForkliftOperating Precautions Storage/Operating EnvironmentPage Maintenance Precautions Qualified Personnel onlyQualified Personnel shall Disposal Do not dispose of the batteries in a fireDo not open or mutilate the batteries Installation Unpacking UPS ClearanceAnchor Bolt Installation Detail Anchor BoltsUPS Wiring External Wiring Diagram11.1 100 kVA Terminal Blocks and Power Cables Block Number Cable Size Tightening TorqueAC Input Bypass Input AC Output Battery YA36L Block Number Cable Size Recommended Fastener TorqueBus Number Cable Size Recommended Fastener Torque UPS Power Cable Knockout Plates Bottom Cable Knockout Plates for 100 KVA T80S3K10KK6XS2HPlate #2 Plate #3 Terminal Knockout Plates for the 300 KVA UPSGrounding Wire External BreakersBe sure to ground the UPS as specified G8000 100 kVA G8000 150/225 kVA Control Wires Signal Name Operation11 Connection Between UPS, Battery Cabinet & Bypass Breaker Grounding Configuration 12 Grounding Configuration with Input Neutral GroundedGrounding Configuration without input neutral Recommended Configuration for delta-inputGrounding Configuration with corner-grounded delta-input 16 Grounding Configuration with CORNER-GROUNDED DELTA-INPUTUPS Specifications General SpecificationMechanical Specification Terms Specification RemarksNominal Capacity 150 kW 225 kW 300 kW Electrical Specification Do not open the front coverOperator Interface UPS may not respond if the button press is too shortKey-Switch and Buttons Graphic Display Panel KEY-SWITCH/OPERATING Buttons13.2 LCD/LED Indicators Graphic Display Panel LCD/LED IndicatorsLCD Indicators Name DescriptionNormal Display AC-VO AC- I O 50%Volt Freq .0Hz 50%AC I/P-V Freq .0Hz BYP I/P-V Freq .0HzDC-V BATT-V BATT- I 0A 32TIMFault Display 09-09-06LCD Scroll AbbreveationsEPO and Control Power Supply Operating Switches Operating the UPSOperation Types Pre-operational CheckPerform the pre-operational check before operating the UPS Startup Procedures Procedure to start the UPS is shown in StepsAC Vo 480 AC Io 50% Switch Power Supply UPS→Bypass Bypass LED is onStop Complete Shutdown DC-V 0 BATT-V 0 BATT-I 0 aChanging Between Float Charge and Equalize Charge Make sure that the Float Charge LED is onMake sure that the Equal Charge LED is on Troubleshooting Emergency Power Off EPOTypes of Errors Faults and Warnings Data Screen 09-09-06LCD Fault & Warning Displays Fault DisplayFault Messages LCD Message Indication DescriptionLCD Message Indication Description LCD Scroll w/ faults or warnings ResetContact Toshiba in the event of malfunction or fault Restoring UPS OperationDo not attempt to modify or relocate the UPS Do not open the front and/or rear panelsPage Page Industrial Division