14.7Changing Between Float Charge and Equalize Charge
The procedure to change the recharge mode between float charge and equalize charge is shown in Steps
See the Note below for an explanation of Float and Equalize charge modes.
LED Key
- LED Off
- LED On
- LED Flash
UPS SUPPLY
AC - Vo 480 V
AC - Io 50%
STEP 1
Make sure that the FLOAT CHARGE LED is “ON”.
AC INPUT
BATTERIES
BYPASS INPUT
CONVERTER
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
UPS
INVERTER
AC
SWITCH
BYPASS
AC OUTPUT
UPS SUPPLY
AC - Vo 480 V
AC - Io 50%
STEP 2
Press FLOAT/EQUAL button for at least 0.5 sec.
Change completed.
AC INPUT
BATTERIES
BYPASS INPUT
CONVERTER
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
UPS
INVERTER
AC
SWITCH
BYPASS
EQUAL CHARGE LED is “ON”.
FLOAT CHARGE LED is “OFF”
AC OUTPUT | STEP 3 |
|
Please wait until procedure is completed.
NOTE
In equalize charge mode, the battery is charged for a programmed period at a specified voltage (depending on the battery spec), rather than the float charge, in order to prevent voltage deviations among battery cells. This should be done once every six months if possible.
The G8000 UPS will automatically perform the equalize recharge after battery backup operation.
G8000 Series Installation and Operation Manual | 61 |