12.Connect the output terminals of the UPS to the load (refer to NEC Article 300 – Wiring Methods and Article 310 – Conductors For General Wiring). Size the branch circuit conductors in accordance with NEC Table 310.16.

Conductor Routing and Grounding

1.Use separate metal conduits for routing the input power, output power, and control circuits.

2.Follow the wire size and tightening torque specifications.

3.Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise.

4.A separate ground cable should be run inside the conduit with the input power, output power, and control circuits.

CAUTION

THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.

XIX

Image 20
Contents Page Important Notice Uninterruptible Power Supply Table of Contents Manual’s Purpose and Scope Page ICES-003 EMC StatementsFCC Part Declaration of Conformity Request General Safety Instructions Safety Alert Symbol / Signal WordsPage Special Symbols Qualified Personnel shall Important Safety InstructionsQualified Personnel only XII Important Safety Instructions contd XIV Instructions Importantes Concernant LA Sécurité Conserver CES InstructionsInspection/Storage/Disposal Storage Maintenance DisposalInstallation Precautions Conductor Routing and Grounding Operating Precautions XXI Introduction System DescriptionBlock diagram General DescriptionPage Free Run Mode Diagnostic TestsSystem Configuration Storage Installation EnvironmentVertical and Wall-mounted Installations with Accessories Rack-mounted Installation with Accessories Stacked UPS Installation with accessories Rear Panel Views 1000VA 1200VA Tower Rear Panel 1000VA Rack mount 1U Rear Panel 1000VA Rack mount 2U Rear Panel Connection to main supply and loads 1000 1200 VA Example of Installation of Plug & Play products Front Panel Settings Settings Options Default RemarksBattery Test TEST? Computer and Alarm Connections RS-232 Standard Interface PortEPO Port emergency power off USB PortNetwork Transient Protector Load SegmentsUser’s Guide to Operations UPS Startup and Shutdown Starting the UPSShutting Down the UPS Button OperationControl Panel functions ON-LINELCD Message Description Normal DisplayUPS Meters Display UPS Configurations Audible Alarms Silencing an AlarmUPS Manual Test Interpreting UPS MessagesTroubleshooting Maintenance Technical Specifications Power Range 1000-1200 VA LV GeneralInput OutputPower Range1000 VA 19 Rack-mount model, LV, 1U & 2U General EnvironmentalPower Range 1000-1200 VA HV General Power Range 1000 VA 19 Rack-mount model, HV, 1U & 2U General StandardTower HV Model Rack-mount HV ModelTower LV Model Rack-mount LV ModelWarranty Information Uninterruptible Power SUPPLIES-UPSLimitations and Exclusions Page Procedure for Defective Product Screening and Disposition Respective warranty period will warranty work be performedModifications