LIMITATIONS AND EXCLUSIONS

This limited warranty shall not cover the UPS, UPS part, or BATTERY during their respective warranty periods, if the following storage, maintenance, installation, operating conditions are not met throughout the warranty periods (5 conditions below):

VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA

INTERNATIONAL CORPORATION UPSREQUIRED OPERATING

CONDITIONS

1.

Temperature

Annual

Average

Temperature per cell < 32°C

Temperature

 

25°C

 

 

 

(89°F) for more than 30

 

 

(77°F)

 

 

 

 

 

 

days

 

 

 

 

 

2.

Maximum number

Discharge time

 

Maximum Number of

of full charge/discharge

 

 

 

Cycles (24 months)

cycles

30 minutes

 

 

69

 

 

15 minutes

 

 

86

 

 

10 minutes

 

 

110

 

 

5 minutes

 

 

130

VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOT TOSHIBA INTERNATIONAL CORPORATION UPS

INSTALLATION AND MAINTENANCE CONDITIONS

3.

Storage

While UPS is in transit or storage it must always be in

suitable temperature (see condition 1).

 

 

4.

External Batteries

Parallel battery string applications must be approved

by TIC in writing.

 

 

5.

Idle Batteries

User must recharge the batteries if not in use

(charged) for more than 6 months.

 

 

34

Image 56
Contents Page Important Notice Uninterruptible Power Supply Table of Contents Manual’s Purpose and Scope Page ICES-003 EMC StatementsFCC Part Declaration of Conformity Request General Safety Instructions Safety Alert Symbol / Signal WordsPage Special Symbols Qualified Personnel shall Important Safety InstructionsQualified Personnel only XII Important Safety Instructions contd XIV Instructions Importantes Concernant LA Sécurité Conserver CES InstructionsInspection/Storage/Disposal Storage Maintenance DisposalInstallation Precautions Conductor Routing and Grounding Operating Precautions XXI Introduction System DescriptionBlock diagram General DescriptionPage Free Run Mode Diagnostic TestsSystem Configuration Storage Installation EnvironmentVertical and Wall-mounted Installations with Accessories Rack-mounted Installation with Accessories Stacked UPS Installation with accessories Rear Panel Views 1000VA 1200VA Tower Rear Panel 1000VA Rack mount 1U Rear Panel 1000VA Rack mount 2U Rear Panel Connection to main supply and loads 1000 1200 VA Example of Installation of Plug & Play products Front Panel Settings Settings Options Default RemarksBattery Test TEST? Computer and Alarm Connections RS-232 Standard Interface PortEPO Port emergency power off USB PortNetwork Transient Protector Load SegmentsUser’s Guide to Operations UPS Startup and Shutdown Starting the UPSShutting Down the UPS Button OperationControl Panel functions ON-LINELCD Message Description Normal DisplayUPS Meters Display UPS Configurations Audible Alarms Silencing an AlarmUPS Manual Test Interpreting UPS MessagesTroubleshooting Maintenance Technical Specifications Power Range 1000-1200 VA LV GeneralInput OutputPower Range1000 VA 19 Rack-mount model, LV, 1U & 2U General EnvironmentalPower Range 1000-1200 VA HV General Power Range 1000 VA 19 Rack-mount model, HV, 1U & 2U General StandardTower HV Model Rack-mount HV ModelTower LV Model Rack-mount LV ModelWarranty Information Uninterruptible Power SUPPLIES-UPSLimitations and Exclusions Page Procedure for Defective Product Screening and Disposition Respective warranty period will warranty work be performedModifications