Release 11/02 | Unpacking and Installing the Panel PC 670/870 |
Also enter the Microsoft Windows "Product Key" of the "Certificate of Authenticity" (COA) in the table. The Product Key can be found on the unit on the power supply cover. The Windows Product Key is necessary should the operating system need to be reinstalled.
SVP number
MLFB number
Microsoft Windows Product Key
1.2Installation of the Panel PC 670/870
Before starting with the installation work, please observe the information below:
Installation notes
Caution
The Panel PC 670/870 is approved for operation in closed rooms.
When installing the Panel PC 670/870, observe the information in Chapter "Technical Data" of the Panel PC 670 or Panel PC 870 Equipment Manual as well as the following points:
•Place the screen in such a way that it is not exposed to direct radiation by sunlight or other light sources.
•Place the screen in an ergonomic position for the user – select a corresponding installation height.
•Position the operating unit and computer so that the air vents in the housing are not covered following installation.
•Ensure that the cabinet/panel has sufficient volume for the air exchange. Further information on this is available in the Panel PC 670/870 Operating Unit Equipment Manual, Chapter 2.4.
•The maximum air inlet temperature for the computer must not exceed 45°C when the unit is operating at maximum capacity.
•These installation notes also apply to the operating unit in a decentralized structure.
•When assembling the Panel PC 670/870, observe the permissible installation angles, depicted in the following diagram.