Unitary UPS (continued)
Main status bits (UPS operating information)
Normal | : inverter powers load and full backup | bit 4C4 = 1 | |
|
| time available |
|
Danger | : inverter does not power load | bit 4C6 = 1 | |
Downgraded | : | malfunction or environment fault | bit 4C5 = 1 |
Load on battery | : | fonctionnement en autonomie | bit 4C7 = 1 |
Operating modes
The following section describes the different states of a
MGETM GalaxyTM 6000 UPS and the addresses of the bits in the system data array.
Normal operation
Load on battery
Normal: | bit 4C4 = 1 |
Danger: | bit 4C6 = 0 |
Downgraded: | bit 4C5 = malfunction dependent |
Load on battery: | bit 4C7 = 0 |
Q1 closed: | bit 40E = 1 |
Rectifier/charger on: | bit 408 = 1 |
QF1 closed: | bit 400 = 1 |
Inverter connected: | bit 484 = 1 |
Q5N closed: | bit 498 = 1 |
Q3BP open: | bit 497 = 0 |
Q4S closed: | bit 496 = 1 |
SS open: | bit 499 = 0 |
K2S open (if available): | bit 494 = 0 |
Normal: | bit 4C4 = 1 |
Danger: | bit 4C6 = 0 |
Downgraded: | bit 4C5 = malfunction dependent |
Load on battery: | bit 4C7 = 1 |
Q1 indifferent: | bit 40E = X (N/A) |
Rectifier/charger off: | bit 408 = 0 |
QF1 closed: | bit 400 = 1 |
Inverter connected: | bit 484 = 1 |
Q5N closed: | bit 498 = 1 |
Q3BP open: | bit 497 = 0 |
Q4S closed: | bit 496 = 1 |
SS open: | bit 499 = 0 |
K2S open (if available): | bit 494 = 0 |
Page 22 - 6739389EN/FB