APC 6000 user manual Inverter, Connectivity

Page 32

System information (continued)

Inverter

Legend:

no entry: not available;

yes: available in this cubicle.

Connectivity

Legend:

no entry: not available;

yes: available in this cubicle;

>800k: on static switch cubicles higher than 800 kVA.

 

inverter

bit meaning

 

JBUS

 

type

 

 

 

information

 

 

address

 

 

 

 

 

 

 

 

 

 

 

hex.

 

 

 

 

 

 

 

 

 

bit=0

bit=1

bit

word

unit.

para.

SS

 

B_Etat_Su_Mut

no overload

overload

440

44

 

yes

 

yes

 

 

B_Etat_Def_Maj_Ond

no fault

fault

441

 

 

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_Etat_Lim_Ond

no limitation

limitation

445

 

 

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_Etat_Suth_Mut

no overload

overload

446

 

 

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_Etat_Aux_Libre

not activated

activated

44C

 

 

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_Etat_Arr_Urg

not activated

activated

44D

 

 

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_Etat_Arr_Forc_Cext

not activated

activated

454

46

 

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_Etat_Inv_Fréq

not activated

activated

465

 

 

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B_Etat_Arr_Prot_Cext

not activated

activated

467

 

 

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connectivity

bit meaning

 

JBUS

type

 

 

 

 

 

 

information

 

 

address

 

 

 

 

 

 

 

 

 

 

 

hex.

 

 

 

 

 

 

 

 

 

 

bit=0

bit=1

bit

word

unit.

par.

SS

 

B_Etat_Su_Ond

no overload

overload

480

48

yes

yes

 

yes

B_Etat_Vent

no fault

ventilation fault

482

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

B_Etat_Ond_Coup

not connected

connected

484

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

B_Etat_Arr_Inter

enable

disable

485

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

B_Etat_Cde_Pilote

not synchro.

synchro.

486

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

B_Etat_Def_Coup

no fault

fault

487

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_Res2_Ht

normal

outside toleran.

48A

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

B_Etat_Arr_Urg

not activated

activated

48D

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

 

 

B_Etat_K2S

open

closed

494

49

 

 

 

 

 

>800k

 

 

 

 

 

 

 

 

 

 

B_Etat_Q4S

open

closed

496

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_Q3BP

open

closed

497

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

B_Etat_Q5N

open

closed

498

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_Cde_Cs_Res2

open

closed

499

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_F_Res2

normal

outside toleran.

49C

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_U_Res2

normal

outside toleran.

49D

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_Freq_Auto

not activated

activated

49F

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_Su_Res2

no overload

overload

4A0

4A

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_Suth_Res2

no overload

overload

4A1

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

B_Etat_Suth_Ond

no overload

overload

4A2

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

B_Etat_Arm_Aux

no fault

fault

4A3

 

yes

yes

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_Sans_Trou

not activated

activated

4A4

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

 

B_Etat_Ver_Sec

not activated

activated

4A5

 

yes

 

 

 

yes

 

 

 

 

 

 

 

 

 

 

 

B_Etat_Nb_Ond_Suff

insufficient

sufficient

4AF

 

 

 

 

 

 

yes

Page 32 - 6739389EN/FB

Image 32
Contents Mgetm GalaxyTM GTC link communication interface2 6739389EN/FB Contents Presentation IntroductionACQ module COM moduleCommunication settings InterfaceJbus protocol Description of request and response frames PrincipleSynchronizing data exchanges Checking received messages on the slave side Functions Function 1 and 2 read N bitsFunction 3 and 4 read N words Function 5 writing a bitFunction 8 reading error diagnosis counters Function 6 writing a wordFunction 11 reading event counters Function 15 writing n consecutive bitsFunction 16 writing n consecutive words MSB LSB MSB LSB MSBCRC 16 algorithm Example of CRC computation Example of CRC 16 computation in C using table lookup Table of Most Significant Bytes for CRC16 ComputationJbus protocol UPS theory of operation Unitary UPSUPS without Mains Parallel connected UPS with Static Switch cubicleOperation without battery Operation with battery Measured quantities Block diagramUnitary UPS Operating modes Normal operation Load on batteryMain status bits UPS operating information Load on Mains Load on bypass Parallel connected UPS Normal operation Load on battery Disconnected Main status bits of system operationsStatic Switch cubicle Normal operation Load on Mains Load on bypass Static SwitchMain indicators of system operations Example of read data array commands sent by the terminal Sample commands List of variable fieldsSystem information Message formatCurrent fields General definitions Signaling fieldTables of measured data Power fields Frequency fields Voltage fieldsRectifier-charger Battery and adjustments fieldsTables of binary data Inverter ConnectivityTable of control devices Global informationGlossary of information descriptors Word addressInverter stack overload 0=no/1=overload Word address 4A Word address 4CWord address 4D Word address 4E summaryC10 call reset 0= not activated / 1=activated Word address C1