Static Switch (continued)
Main indicators of system operations
Normal | : charge alimentée par l'onduleur | bit 4C4 = 1 | |
Danger | : | charge non alimentée par l'onduleur | bit 4C6 = 1 |
Downgraded | : | anomalie de fonctionnement | bit 4C5 = 1 |
|
| ou défaut d'environnement |
|
|
|
|
|
Operating modes
The following section describes the different states of a Static Switch cubicle and the addresses of the bits in the system data array.
Normal operation
Load on Mains 2
Load on bypass
Normal:
Danger:
Downgraded: Q5N closed: Q3BP open: Q4S closed: SS open:
K2S open (if available): Inverters connected to load:
Normal:
Danger:
Downgraded:
Q5N closed:
Q3BP open:
Q4S closed:
SSclosed (if K2S not available): K2S closed (if available): Inverters not connected to load:
Normal:
Danger:
Downgraded: Q5N open: Q3BP closed: Q4S indifferent: CS indifférent: SS indifferent:
Inverter connected indifferent:
bit 4C4 = 1 bit 4C6 = 0
bit 4C5 = malfunction dependent bit 498 = 1
bit 497 = 0 bit 496 = 1 bit 499 = 0 bit 494 = 0 bit 4AE = 1
bit 4C4 = 0 bit 4C6 = 1
bit 4C5 = X (N/A) bit 498 = 1
bit 497 = 0 bit 496 = 1 bit 499 = 1 bit 494 = 1 bit 4AE = 0
bit 4C4 = 0 bit 4C6 = 1
bit 4C5 = X (N/A) bit 498 = 0
bit 497 = 1
bit 496 = X (N/A) bit 499 = X (N/A) bit 494 = X (N/A) bit 4AE = X (N/A)
6739389EN/FB - Page 27