APC 6000 user manual Inverter stack overload 0=no/1=overload

Page 35

System information (continued)

41B: battery equalization (0=not active/1=active)

The rectifier-charger has been manually switched to equalization mode, to equalize battery cell voltages. This action stops all inverters powered by the battery (if they were not already stopped).

41E: operation on engine- generator set (0=not activated / 1=activated)

Indicates that the rectifier-charger is supplied by an engine-generator set and not by the normal Mains 1 power supply.

Word address: 44

440:inverter stack overload (0=no/1=overload)

Indicates an overload condition due to a load power factor exceeding 0.9.

441:major inverter fault (0=no/ 1=fault)

Informs the user of an inverter fault requiring after-sales servicing.

445:inverter output current limiting (0=no/1=active) Informs the user that an overload exceeding 1.6 In has occurred at the output: the inverter stops operating.

446:inverter thermal overload (0=no/1=overload)

Informs the user that the output is overloaded by a factor between 1 and 1.6 In: the inverter stops operating.

44C: outside contact (0=not activated/1=activated)

Normally open switch. Initiates the actions that have been configured using the after-sales "Soft Tunor" computer software. Possible actions when activated:

no action;

inverter off;

forced inverter shutdown;

conditional inverter shutdown;

frequency change (when powering on the unit) with respect to the frequency configured by the after-sales "Soft Tunor" computer software (i.e. 50Hz to 60Hz or vice versa).

44D: emergency off switch (0=not activated/1=activated) Normally-closed switch connected to the units. When activated, the rectifier-charger circuits and the inverters stop operating. The "QF1" battery circuit breaker is also opened. If the "emergency off" also trips the protection devices to disconnect the units from Mains 1 and Mains 2, the load no longer receives power and the units are completely disconnected.

Word address: 46

464:forced inverter shutdown (0=not activated / 1=activated) Indicates to the user that a shutdown of the inverter will result in transfer of the load to Mains 2 with the risk of a 0.8 second interruption in the supply of power to the load.

465:frequency conversion (0=not activated / 1=activated) Indicates that the

MGETM GalaxyTM 6000 UPS is operating as a frequency converter between the input and the output (50 Hz / 60 Hz).

466:conditional inverter shutdown (0=not activated / 1=activated)

Indicates to the user that a shutdown of the inverter will take place only if the load transfer conditions to Mains 2 are correct to avoid an interruption in the supply of power to the load.

Word address: 48

480:inverter overload (0=no/ 1=overload)

Informs the user that the load is drawing more than the rated UPS output.

482:ventilation of the battery cabinets (0=no fault / 1=fault) Indicates to the user that ventilation in a battery cabinet is incorrect due to a fan fault or shutdown. This fault does not result in UPS shutdown. This information is available only on European versions of the

MGETM GalaxyTM 6000 UPS.

484:inverter connected to the load (0=not connected/ 1=connected)

The inverter is operating and powers the load.

485:inverter off disable (0=enabled/1=disabled) The inverter off command is disabled.

486:synch with Mains 2 (0=not synch/1=synch)

The inverter may operate without its frequency synchronized to that of Mains 2 (i.e. free-running operation); in this case, it operates at an accurate (within 0.05 Hz) fixed frequency. Alternatively, the inverter may be operated with its frequency synchronized to that of Mains 2.

487:transfer fault (0=no fault/ 1=fault)

Informs the user of a fault on the static switch, used to transfer the load between Mains 2 and inverter output. After-sales servicing is required.

48A: Mains 2 voltage outside tolerances (0=normal / 1=outside tolerances)

Indicates to the user that the Mains 2 backup power supply voltage is outside tolerances. A transfer of the load to the Mains 2 backup power supply will result in a 0.8 second interruption in the supply of power to the load or may not take place.

48D: emergency off switch (0=not activated/1=activated)

Normally-closed switch connected to the units. When activated, the rectifier-charger circuits and the inverters stop operating. The "QF1" battery circuit breaker is also opened.

If the "emergency off" also tripped the protection devices to disconnect the units from Mains 1 and Mains 2, the load no longer receives power and the units are completely disconnected.

6739389EN/FB - Page 35

Image 35
Contents GTC link communication interface Mgetm GalaxyTM2 6739389EN/FB Contents COM module PresentationIntroduction ACQ moduleInterface Communication settingsJbus protocol Description of request and response frames PrincipleSynchronizing data exchanges Checking received messages on the slave side Function 1 and 2 read N bits FunctionsFunction 5 writing a bit Function 3 and 4 read N wordsFunction 6 writing a word Function 8 reading error diagnosis countersFunction 15 writing n consecutive bits Function 11 reading event countersMSB LSB MSB LSB MSB Function 16 writing n consecutive wordsCRC 16 algorithm Example of CRC computation Table of Most Significant Bytes for CRC16 Computation Example of CRC 16 computation in C using table lookupJbus protocol Unitary UPS UPS theory of operationUPS without Mains Parallel connected UPS with Static Switch cubicleOperation without battery Operation with battery Measured quantities Block diagramUnitary UPS Operating modes Normal operation Load on batteryMain status bits UPS operating information Load on Mains Load on bypass Parallel connected UPS Main status bits of system operations Normal operation Load on battery DisconnectedStatic Switch cubicle Normal operation Load on Mains Load on bypass Static SwitchMain indicators of system operations Message format Example of read data array commands sent by the terminalSample commands List of variable fields System informationCurrent fields General definitions Signaling fieldTables of measured data Voltage fields Power fields Frequency fieldsRectifier-charger Battery and adjustments fieldsTables of binary data Connectivity InverterGlobal information Table of control devicesWord address Glossary of information descriptorsInverter stack overload 0=no/1=overload Word address 4C Word address 4AWord address 4E summary Word address 4DWord address C1 C10 call reset 0= not activated / 1=activated