System information (continued)
41B: battery equalization (0=not active/1=active)
The
41E: operation on engine- generator set (0=not activated / 1=activated)
Indicates that the
Word address: 44
440:inverter stack overload (0=no/1=overload)
Indicates an overload condition due to a load power factor exceeding 0.9.
441:major inverter fault (0=no/ 1=fault)
Informs the user of an inverter fault requiring
445:inverter output current limiting (0=no/1=active) Informs the user that an overload exceeding 1.6 In has occurred at the output: the inverter stops operating.
446:inverter thermal overload (0=no/1=overload)
Informs the user that the output is overloaded by a factor between 1 and 1.6 In: the inverter stops operating.
44C: outside contact (0=not activated/1=activated)
Normally open switch. Initiates the actions that have been configured using the
◗no action;
◗inverter off;
◗forced inverter shutdown;
◗conditional inverter shutdown;
◗frequency change (when powering on the unit) with respect to the frequency configured by the
44D: emergency off switch (0=not activated/1=activated)
Word address: 46
464:forced inverter shutdown (0=not activated / 1=activated) Indicates to the user that a shutdown of the inverter will result in transfer of the load to Mains 2 with the risk of a 0.8 second interruption in the supply of power to the load.
465:frequency conversion (0=not activated / 1=activated) Indicates that the
MGETM GalaxyTM 6000 UPS is operating as a frequency converter between the input and the output (50 Hz / 60 Hz).
466:conditional inverter shutdown (0=not activated / 1=activated)
Indicates to the user that a shutdown of the inverter will take place only if the load transfer conditions to Mains 2 are correct to avoid an interruption in the supply of power to the load.
Word address: 48
480:inverter overload (0=no/ 1=overload)
Informs the user that the load is drawing more than the rated UPS output.
482:ventilation of the battery cabinets (0=no fault / 1=fault) Indicates to the user that ventilation in a battery cabinet is incorrect due to a fan fault or shutdown. This fault does not result in UPS shutdown. This information is available only on European versions of the
MGETM GalaxyTM 6000 UPS.
484:inverter connected to the load (0=not connected/ 1=connected)
The inverter is operating and powers the load.
485:inverter off disable (0=enabled/1=disabled) The inverter off command is disabled.
486:synch with Mains 2 (0=not synch/1=synch)
The inverter may operate without its frequency synchronized to that of Mains 2 (i.e.
487:transfer fault (0=no fault/ 1=fault)
Informs the user of a fault on the static switch, used to transfer the load between Mains 2 and inverter output.
48A: Mains 2 voltage outside tolerances (0=normal / 1=outside tolerances)
Indicates to the user that the Mains 2 backup power supply voltage is outside tolerances. A transfer of the load to the Mains 2 backup power supply will result in a 0.8 second interruption in the supply of power to the load or may not take place.
48D: emergency off switch (0=not activated/1=activated)
If the "emergency off" also tripped the protection devices to disconnect the units from Mains 1 and Mains 2, the load no longer receives power and the units are completely disconnected.
6739389EN/FB - Page 35