APC 6000 user manual System information, Message format, Sample commands List of variable fields

Page 28

System information

Message format

This section describes the messages exchanged between the "GTC link" communication interface and the external computer based on the JBUS protocol.

The length of time after which a message must be interpreted as "not understood" depends on the type of command sent.

The table opposite lists maximum response times:

Data rate

1200 Baud

2400 Baud

4800 Baud

9600 Baud

status information only

0,5 s

0,25 s

0,12 s

0,06 s

 

 

 

 

 

all measurements

2 s

1 s

0,5 s

0,25 s

 

 

 

 

 

 

 

 

 

 

Response time of event (independent of data rate)

 

 

- inverter start-up and connect

:

30 s

 

 

 

 

 

 

- rectifier-charger startup

 

:

30 s

 

 

 

 

 

- rectifier-charger or inverter stop

:

30 s

 

 

 

 

 

 

Example of read data array commands sent by the terminal

(address: 20H)

For the "responses", refer to the "JBUS protocol" section function 1 and 3.

request

station

function

data

length

CRC 16

 

 

code

address

 

 

read voltage

20

03

0140

0015

82 9C

array

 

 

 

 

 

(21 values)

 

 

 

 

 

read current

20

03

0100

000F

28 03

array

 

 

 

 

 

(15 values)

 

 

 

 

 

read global

20

01

04C0

000B

7A 70

state bits

 

 

 

 

 

(11 bits)

 

 

 

 

 

Sample commands

List of variable fields

(same for all cubicle types)

The binary data and binary commands can be accessed bit or word-wise.

The word address and position of the bit in the word can be determined from the bit address:

hundreds and tens digit of bit address = word address;

least significant digit of bit address = bit position.

command

station

function

bit

data

not

CRC 16

 

 

code

address

 

used

 

charger on

20

05

0C00

FF

00

89 DB

 

 

 

 

 

 

 

charger off

20

05

0C01

FF

00

D8 1B

 

 

 

 

 

 

 

inverter on

20

05

0C04

FF

00

C8 1A

 

 

 

 

 

 

 

inverter off

20

05

0C05

FF

00

99 DA

 

 

 

 

 

 

 

 

JBUS fields

address in hexadecimal

access

 

 

start

 

end

 

 

 

 

 

 

signaling

0

 

5

read / write

signaling

6

 

F

read

binary data

40

 

BF

read

commands

C0

 

DF

read / write

counters

E0

 

FF

read

currents

100

 

13

read

voltages

140

 

17

read

powers

180

 

19F

read

frequencies

1A0

 

1BF

read

battery

1C0

 

1DF

read

adjustments

200

 

2FF

read

maintenance

300

 

3FF

read

Page 28 - 6739389EN/FB

Image 28
Contents Mgetm GalaxyTM GTC link communication interface2 6739389EN/FB Contents Presentation IntroductionACQ module COM moduleCommunication settings InterfaceJbus protocol Synchronizing data exchanges PrincipleDescription of request and response frames Checking received messages on the slave side Functions Function 1 and 2 read N bitsFunction 3 and 4 read N words Function 5 writing a bitFunction 8 reading error diagnosis counters Function 6 writing a wordFunction 11 reading event counters Function 15 writing n consecutive bitsFunction 16 writing n consecutive words MSB LSB MSB LSB MSBCRC 16 algorithm Example of CRC computation Example of CRC 16 computation in C using table lookup Table of Most Significant Bytes for CRC16 ComputationJbus protocol UPS theory of operation Unitary UPSOperation without battery Parallel connected UPS with Static Switch cubicleUPS without Mains Operation with battery Unitary UPS Block diagramMeasured quantities Main status bits UPS operating information Normal operation Load on batteryOperating modes Load on Mains Load on bypass Parallel connected UPS Normal operation Load on battery Disconnected Main status bits of system operationsStatic Switch cubicle Main indicators of system operations Static SwitchNormal operation Load on Mains Load on bypass Example of read data array commands sent by the terminal Sample commands List of variable fieldsSystem information Message formatTables of measured data General definitions Signaling fieldCurrent fields Power fields Frequency fields Voltage fieldsTables of binary data Battery and adjustments fieldsRectifier-charger Inverter ConnectivityTable of control devices Global informationGlossary of information descriptors Word addressInverter stack overload 0=no/1=overload Word address 4A Word address 4CWord address 4D Word address 4E summaryC10 call reset 0= not activated / 1=activated Word address C1