APC 6000 user manual Word address C1, C10 call reset 0= not activated / 1=activated

Page 38

System information (continued)

The telephone number is reinstated:

on reception of a new communication configuration using the Soft Tunor after-sales-support computer tool,

when the "GTCZ" or "GT2Z" communication board is de- energised.

Word address: C1

C10: call reset (0= not activated / 1=activated)

Call reset command issued by the central telemonitoring site. The information bits that provoked the call to the central telemonitoring site are reset.

C11: return call (0= not activated / 1=activated)

Return call command issued by the central telemonitoring site. The UPS site recalls the central telemonitoring site following a time delay of approximately 30 seconds.

C14: status change reset (0= not activated / 1=activated)

Indicates that the central telemonitoring site issues a reset command for the status change bit at address 4EF.

Page 38 - 6739389EN/FB

Image 38
Contents Mgetm GalaxyTM GTC link communication interface2 6739389EN/FB Contents ACQ module PresentationIntroduction COM moduleCommunication settings InterfaceJbus protocol Description of request and response frames PrincipleSynchronizing data exchanges Checking received messages on the slave side Functions Function 1 and 2 read N bitsFunction 3 and 4 read N words Function 5 writing a bitFunction 8 reading error diagnosis counters Function 6 writing a wordFunction 11 reading event counters Function 15 writing n consecutive bitsFunction 16 writing n consecutive words MSB LSB MSB LSB MSBCRC 16 algorithm Example of CRC computation Example of CRC 16 computation in C using table lookup Table of Most Significant Bytes for CRC16 ComputationJbus protocol UPS theory of operation Unitary UPSUPS without Mains Parallel connected UPS with Static Switch cubicleOperation without battery Operation with battery Measured quantities Block diagramUnitary UPS Operating modes Normal operation Load on batteryMain status bits UPS operating information Load on Mains Load on bypass Parallel connected UPS Normal operation Load on battery Disconnected Main status bits of system operationsStatic Switch cubicle Normal operation Load on Mains Load on bypass Static SwitchMain indicators of system operations System information Example of read data array commands sent by the terminalSample commands List of variable fields Message formatCurrent fields General definitions Signaling fieldTables of measured data Power fields Frequency fields Voltage fieldsRectifier-charger Battery and adjustments fieldsTables of binary data Inverter ConnectivityTable of control devices Global informationGlossary of information descriptors Word addressInverter stack overload 0=no/1=overload Word address 4A Word address 4CWord address 4D Word address 4E summaryC10 call reset 0= not activated / 1=activated Word address C1