Datalogic Scanning C-BOX 200 5 RS485 Bus Termination, Termination resistance switch

Page 21

C-BOX 200

DATALOGIC

2.4.5 RS485 Bus Termination

ON

OFF

S2

Figure 2.11 - Termination resistance switch

The switch S2 enables or disables the insertion of the bus termination resistor for RS485 Half Duplex Multidrop applications.

CAUTION

In Multiplexer applications the termination resistor must be enabled ONLY on the last device of the chain, the farthest away from the Multiplexer (assuming the Multiplexer is the first device of the chain). On all the other devices this resistor MUST NOT be enabled (S2 = OFF).

Normally it is not necessary to enable the terminator resistor (S2 always OFF); it is suggested only in applications where the communication speed or the bus length are critical parameters.

12 - Installation

Image 21
Contents BOX BOX Installation Manual821000560 Contents Guide to Installation Figure a General ViewFigure B Power Supply Safety PrecautionsViii Description General FeaturesPackage Contents InstallationOpening the C-BOX Opening the DeviceOverall dimensions Mechanical InstallationMounting C-BOX System layout Electrical Connections and SetupPower switch ON/OFF positions Power SupplySystem cable connections System WiringRefer to the scanner Installation Manual for details Chassis grounding Chassis Grounding Jumper SettingsMultidrop Address Selection 10 Rotary switches5 RS485 Bus Termination 11 Termination resistance switchBOX Connection to a Multiplexer13 OM4000 jumpers 7 OM4000 Jumper Settings9-PIN Scanner Auxiliary Serial Interface 14 9-pin male connector Pin connector pinout Name FunctionOperating Modes Scanner RequirementsGET Send 1 GET/SEND Buttons15 LED Indicators LED IndicatorsEnvironmental Features Technical Features