Communications
PLC/CPU Connection
Symptom | Possible Causes | Solution |
|
|
|
CIMPLICITY does not | The system is attempting to | 1. With the PLC powered up and |
communicate with a PLC that has | communicate with a | connected to the Display Station, |
been autoconfigured | using the SNP driver and a | establish communication between |
(AUTOCONFIG/DEFAULT/I/O | CIMPLICITY project. | the Display Station and PLC via |
error). |
| the |
|
| 2. Using a |
|
| Programmer, toggle the Default |
|
| I/O (Enable or Disable) |
|
| configuration parameter for the |
|
| CPU. Communications between |
|
| the Display Station and the PLC |
|
| will be stopped. (Communications |
|
| are stopped when you toggle from |
|
| Enable to Disable, or vice versa.) |
|
| 3. Power cycle the PLC. |
|
|
|
Communications between the host | COM port not configured in | Verify that the COM port is |
computer and the controller are | system. | configured in the system. |
unsuccessful. |
|
|
|
|
|
| Cabling between computer and | Verify that the cable between the |
| controller. | computer and the controller is |
|
| correctly wired. |
|
|
|
| Baud rate and parity configured | Verify that the baud rate and |
| incorrectly. | parity on the computer are |
|
| consistent with those on the |
|
| controller. |
|
|
|
| Wrong address. | Verify that the slave address is |
|
| correct. |
|
|
|
30 | CIMPLICITY® Display Station Touch Display: IC752CTD400/450 – March 1998 |