SECONDARY MENU (The fixed characteristics of the system).

PRESS

DISPLAY

ACTION

SEL hold until

p-n1

SET TO 0 – REVERSE ACTION

SEL hold until

p-n2

SET TO 2 = TYPE J THERMOCOUPLE

SEL

p-dFDIGITAL FILTER

SET TO 5

SEL

P-SLLOWER LIMIT

SET TO -40 (-40ºC)

SEL

P-SUUPPER LIMIT

SET TO 350 (350ºC)

SEL

P-AH ALARM

SET TO 0

SEL

P-AnHYTERESIS

SET TO 5

SEL

P-dPPROG DECIMAL

SET TO 0

SEL

PVOF PROCESS OFFSET

LEAVE AT 0

SEL

SVOF SET POINT OFFS

LEAVE AT 0

SEL

P-F

SET TO 0 (0 = oC, 1 = oF)

SEL

P-n1

ALREADY CONFIGURED

SEL hold until RETURNS TO MAIN MENU

 

SEL

PV/SV

SET DISPLAY TO 315 C

SEL hold until

P PROP BAND

ALREADY CONFIGURED

SEL

SCROLL TO A7

SET TO 1 (AUTOTUNE )

34

05386 Rev. D

Image 38
Contents M200EU-NOy Converter Page Page Page Safety Messages 05386 Rev. D Table of Contents List of Figures List of TablesIntroduction This page intentionally left blank 05386 Rev. D Electrical and Pneumatic Connections Getting StartedUnpacking Rear Panel Pneumatic Connections Initial Operation Final Test and Calibration ValuesThis page intentionally left blank 05386 Rev. D SPECIFICATIONS, Warranty SpecificationsWarranty Teledyne Advanced Pollution INSTRUMENTATION, INCM200EU-NOYCONVERTER Principle of OperationThis page intentionally left blank 05386 Rev. D Calibration and ZERO/SPAN Checks Calibration or Cal Check Procedure Span Calibration Procedure This page intentionally left blank 05386 Rev. D Maintenance Maintenance ScheduleReplacing the Sample Particulate Filters Replacing the Particulate Filter Checking Analyzer Flow Rate Replacing the ConverterNOy Converter Assembly Inspecting Pneumatic Lines Pneumatics diagram standard and Z/S option Pneumatic diagram OPT 86 option Sample Driers Checking for Leaks This page intentionally left blank 05386 Rev. D TROUBLESHOOTING, Adjustments Operation Verification Diagnostic Techniques Pneumatic system is diagramed 05386 Rev. D Setting the Converter Temperature Bypass Pump Diagnostic ProceduresLOC Lock AH Alarm Electrical Diagram This page intentionally left blank 05386 Rev. D M200EU-NOYSPARE Parts List Description