Whirlpool 8316558 Gas requirements, Observe ALL Governing Codes and Ordinances

Page 4

An exhaust hood should cap the exhaust vent to prevent exhausted air from returning into the dryer. The outlet of the hood must be at least

12 inches (30.5 cm) from the ground or anything else that may be in the path of the exhaust.

Four-inch outlet hood is preferred. However, a 2-1/2-inch (6.4 cm) outlet exhaust hood may be used. A

2-1/2-inch (6.4 cm) outlet creates greater back pressure than other hood types. For permanent installation, a stationary exhaust system is required.

A main exhaust vent can be used for exhausting a group of dryers. Main exhaust vent should be sized to remove 200 CFM of air per dryer. Large-capacity lint screens of proper design may be used in the main exhaust vent if checked and cleaned frequently. The room where the dryers are located should have make-up air equal to or greater than the CFM of all the dryers in the room.

 

exhaust

vent

 

 

 

exhaust

vent

dryer

 

 

 

30° max.

dryer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

air flow

 

 

 

main collector vent

 

 

 

 

 

 

 

 

 

dryer

 

 

30° max.

dryer

 

 

30° max.

exhaust

 

 

 

exhaust

 

 

 

 

 

 

vent

 

vent

 

 

 

 

 

 

 

 

Back-draft Damper Kits, Part No. 3391910, are available from your Whirlpool dealer and should be installed in each dryer's exhaust vent to prevent exhausted air from returning into the dryers and to keep the exhaust in balance within the main exhaust vent. Unobstructed air openings are required.

Each exhaust vent should enter the main vent at an angle pointing in the direction of the airflow. Vents entering from the opposite side should be staggered to reduce the exhausted air from interfering with the other vents.

The maximum angle of each vent entering the main vent should be no more than 30°.

Keep air openings free of dry cleaning fluid fumes. Fumes create acids which, when drawn through the dryer heating units, can damage dryers and loads being dried.

A clean-out cover should be located on the main exhaust vent for periodically cleaning of the exhaust system.

An exhaust hood should cap the outside end of the main vent to prevent exhausted air from returning to the dryers. If an exhaust hood cannot be used, the outside end of the main duct should have a sweep elbow directed downward. If the main vent travels vertically through the roof, rather than through the wall, install 180° sweep elbow on the end of vent at least 2 feet (61 cm) above the highest part of the building. The opening wall or roof shall have a diameter 1/2 inch (1.3 cm) larger than the exhaust vent diameter. The exhaust vent should be centered in the opening.

exhaust

 

 

 

wall

hood or

 

 

 

 

 

 

 

 

sweep

 

 

 

 

 

elbow

 

 

horizontal vent

 

 

 

 

 

 

 

main exhaust vent

wall

180°

sweep

2 ft. (61 cm)elbow min. above

highest point of

building

ventvertical

 

main collector

 

 

vent

 

 

 

 

 

 

 

 

roof

Do Not install screening or cap over end of vent.

Gas Dryer

Gas requirements

WARNING

Explosion Hazard

Use a new AGA or CSA approved gas supply line.

Install a shut-off valve.

Securely tighten all gas connections.

If connected to LP, have a qualified person make sure gas pressure does not exceed 13" (33 cm) water column. Examples of a qualified person include licensed heating personnel, authorized gas company personnel, and authorized service personnel.

Failure to do so can result in death, explosion, or fire.

OBSERVE ALL GOVERNING CODES AND ORDINANCES.

A.This installation must conform with local codes, or in absence of local codes with the National Fuel Gas Code ANSI Z223.1/NFPA 54 or the CAN/CGA - B149 installation codes.

B.The design of this dryer has been certified by the CSA International for use at altitudes up to 10,000 feet (3048 m) above sea level at the B.T.U. rating indicated on the model/serial plate. Burner input adjustments are not required when the dryer is operated up to this elevation.

When installed above 10,000 feet (3048 m), a four percent (4%) reduction of the burner B.T.U. rating shown on the model/serial plate is required for each 1,000 foot (305 m) increase in elevation. For assistance when converting to other gas types and/or installing above 10,000 feet (3048 m) elevation, contact your local service company.

Page 4

Image 4
Contents Installation Instructions Before you start It is your responsibility toTo change to a 30- or 60-minute timingcam Exhaust Hood TypeGas requirements Observe ALL Governing Codes and OrdinancesElectrical requirements Recommended ground methodNow Start Electrical requirements Direct wire U.S. only Power supply cordGrounding Instructions Four-wire connection Three-wire connection Direct Wire or Power Supply Cord Recessed area and closet installation instructions Product dimensions Bottom ExhaustInstructions d’installation Avant de commencer Votre sécurité et celle des autres est très importanteSpécifications du système d’évacuation Type DE Bouche DE DéchargeSécheuse à gaz SpécificationsInstallation électrique Méthode recommandée de liaison à la terreCommencer Sécheuse électrique Cablâge direct Cordon d’alimentationInstructions DE Liaison À LA Terre Circuit à quatre conducteurs… Cordon D’ALIMENTATIONCircuit à trois conducteurs… Cordon D’ALIMENTATIONSi les codes locaux ne permettent pas Déménagement de la Sécheuse Instructions d’entretienSi vous avez besoin ’aide Dimensions du produit Évacuation PAR LE BAS