ALTERNATECONNECTION:

If local codes do not permit the

connection of a frame-grounding

conductor to the neutral wire:

STEP 1. Make sure the power supply to the dryer is off.

STEP 2. Make sure the power supply cord or direct wire cable is in place (see steps 1-3 on pages 12-13 for power cord connections or steps 1-3 on pages 13-14 for ,direct wire connection).

STE=P 3, Remove the neutral grounding wire (green/yellow wire) from external grounding connector screw. Loosen or remove terminal block screws. Connect

neutral grounding wire and the neutral wire (white or center) of power supply cord or direct wire cable under the center screw of the terminal block.

External

ground connector

STEP 4, Connect the other two wires to outer terminal block screws. Tighten all terminal block screws firmly.

STEP 5, Tighten the strain relief screws.

STEP 6, Insert tab of terminal block

cover into slot of the dryer rear panel. Secure cover with hold-down screw.

STEP 7, Connect separate copper grounding wire from external ground connector to an adequate ground. If codes permit and a separate grounding wire is used, it is recommended that a qualified electrician determine that the grounding path is adequate.

Proceed with Exhaust Installation. See "CONNECT EXHAUST" on

page 19.

Neutral groundingwire (green/yellow)

Groundingpath determinedbya qualiliedelectrician

Alternate 3-Wire Connection with

External-Grounding Conductor

15

Image 15
Contents Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A OwnersManual Installation InstructionsKeep this book and your Sears Full 1-YEAR Warranty on Mechanical and Electrical Parts Your safety and the safety of others is very importantYour Safety is Important to US Installation Overview Select LocationParts Needed If making a direct wire connection Tools Needed Parts Needed Optional depending Connect Exhaust pgs Tools Needed Parts NeededSelect Location for Your Dryer Standard InstallationProduct Dimensions Recessed AREA/CLOSET Installation InstructionsInstall Leveling Legs Electrical Connection Options If Your Home Has Wire electrical ReceptacleIt is your responsibility Quincy, MassachusettsNEI THREE-WIREELECTRICALExlernal ground ConnectorWhite neutral wire Wire Connection withExhaust Conductor to the neutral wire External Ground connectorAlternateconnection Neutral III. Make FOUR-WIREFour-wire receptacle Nema Type 14-30R Electrical Connection to ReceptacleNeutral WireGreenwire PowersupplyIV. FOUR-WIRE Electrical Connection Direct Wire BarecopperwireNeutral WhiteneutralwireRoute the Vent Typical installations for left or right side exhaustingDetermine Vent Length Exhaust Hood TypeStep Flexible metalvent IDryerDucttape & clamp Offset Connections with Close Clearances Loop SystemPeriscope System Final Steps Review InstallationStarting Your Dryer STOPPING/RESTARTINGYour Dryer Touch UP Cycle Cycle DescriptionAuto DRY Cycle Timed DRY CycleCottons and Linens FABRIC/TEMPERATURE ControlDelicate Fabrics Using AIR DRY/AIR FluffTo use AIR Fluff AIR FluffCool Down Push to Start ButtonUsing Wrinkle Guard WrinkleguardLint Alert HEATEDDR.RACK Preparing Clothes For Drying Choosing Load SizesSuper Capacity Plus Dryers Drying Tips Using Dryer FABRICSOFrENERSCleaning Your Dryer ExteriorInterior To wash Cleaning the Lint ScreenTo clean Wash Lint Screen As NeededChecking for AIR Flow Obstruction To remove accumulated lint from Inside the dryerRemoving Accumulated Lint Changing the Drum Light Moving CareVacation Care Not Drying Wrinkled ContLoad is overdried Stains on LoadFor more information, call We Service What We SellSears Maintenance Agreement Kenmore DryersPage 8F,eLR8