ADC AD-115ES installation manual Outside Ductwork Protection

Page 19

Outside Ductwork Protection

To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward should be installed where the exhaust exits the building. If the exhaust ductwork travels vertically up through the roof, it should be protected from the weather by using a 180° turn to point the opening downward. In either case, allow at least twice the diameter of the duct between the duct opening and the nearest obstruction.

IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust ductwork.

2.Single Dryer Venting

When possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct should be laid out in such a way that the ductwork travels as directly as possible to the outdoors with as few turns as possible. It is suggested that the use of 90° turns in ducting be avoided; use 30° and/or 45° angles instead. The shape of the exhaust ductwork is not critical as long as the minimum cross section area is provided.

IMPORTANT: Minimum duct size for a gas, electric, or steam dryer with a vertical run and not more than three (3) elbows (including dryer connection and outside outlets) is 16-inches (40.64 cm) for a round duct or 14-1/2” by 14-1/2” (36.83 cm by 36.83 cm) for a square duct. DUCT SIZE MUST NOT BE REDUCED ANYWHERE DOWNSTREAM OF DRYER.

IMPORTANT: Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust duct area must be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water column (W.C.).

It is suggested that the ductwork from each dryer (minimum 14-inches [35.56 cm]) not exceed 20 feet (6.09 meters) with no more than three (3) elbows (including dryer connections and outside exhaust outlets). If the ductwork exceeds 20 feet (6.09 meters) or has numerous elbows, the cross section area of the ductwork must be increased in proportion to the length and number of elbows in it. In calculating duct size, the cross section area of a square or rectangular duct must be increased by twenty percent (20%) for each additional 20 feet (6.09 meters). The diameter of a round exhaust duct should be increased ten percent (10%) for each additional 15 feet (4.57 meters). Each 14-inch (35.56 cm) 90° elbow is equivalent to 30 feet (9.14 meters) and each 16-inch (40.64 cm) 90° elbow is equivalent to 36 feet (10.97 meters).

113202 - 10

www.amdry.com

15

Image 19
Contents AD-115ES Installation Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Safety PrecautionsStandard Specifications SPECIFICATIONS/COMPONENT IdentificationSpecifications Gas, Electric, and Steam Component Identification 113202 Location Requirements Installation ProceduresUnpacking and Setting UP American Dryer Corp 113202 This Exhaust Duct Transition Piece Must be Installed First Fresh AIR Supply Requirements Dryer Enclosure RequirementsGeneral Exhaust Ductwork Information Exhaust RequirementsAmerican Dryer Corp 113202 Outside Ductwork Protection American Dryer Corp 113202 Electrical Information Reversing, 3ø Motor Gas and Steam Reversing, 3ø Motor Electric American Dryer Corp 113202 GAS Information Type of GAS Type of GAS American Dryer Corp 113202 Steam Information Operating Steam PressureCompressed Air Supply Air Pressure Steam Damper System113202 Before YOU Start Check Local Codes and Permits Water Information113202 Typical Water Supply Preparation for Operation and START-UP Preoperational Test Basket Tumbler Coating Preoperational Instructions Dual Timer DryersShutdown Instructions Reversing Timer SPIN/DWELL AdjustmentsService SERVICE/PARTS InformationParts Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyAmerican Dryer Corp 113202 Cleaning Routine MaintenanceSuggested Cleaning Schedule Lubrication AdjustmentsData Label Information Procedure for Functional Check Replacement Components 113202 Phase Manual Reset Burner HI-LIMIT InstructionsDual Timer 113202 ADC Part No 10 12/10/08