ADC AD-115ES installation manual Preparation for Operation and START-UP

Page 35

The manual ball cock shutoff valve must be located outside of the dryer at a distance from the dryer where it is easily accessible.

3.Electrical Requirements

No independent external power source or supply connection is necessary. The 24 volt power to operate the fire suppression system is accomplished internally in the dryer (from the dryer controls).

WARNING: Electrical power must be provided to the dryer at ALL times. If the main electrical power supply to the dryer is disconnected, the fire suppression system is

INOPERATIVE!!

J. PREPARATION FOR OPERATION AND START-UP

The following items should be checked before attempting to operate the dryer:

1.Read ALLCAUTION,” “WARNING,” and “DIRECTION” labels attached to the dryer.

2.Check incoming supply voltage to be sure that it is the same as indicated on the dryer data label. In case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service exactly.

3.GAS MODELS – check to ensure that the dryer is connected to the type of heat or gas indicated on the dryer data label.

4.GAS MODELS – the sail switch damper assembly was installed and adjusted at the factory prior to shipping. However, each sail switch adjustment must be checked to ensure that this important safety control is functioning.

5.Check to be sure drive belts between idler pulley and motor pulley have been reconnected.

6.GAS MODELS – be sure that ALL gas shutoff valves are in the open position.

7.Be sure ALL back panels (guards) and electric box covers have been replaced.

8.Check ALL service doors to ensure that they are closed and secured in place.

9.Be sure lint drawer is securely in place.

NOTE: LINT DRAWER MUST BE ALLTHE WAY IN PLACE TO ACTIVATE SAFETY SWITCH OTHERWISE THE DRYER WILL NOT START.

10.Rotate the basket (tumbler) by hand to be sure it moves freely.

11.Check bolts, nuts, screws, terminals, and fittings for security.

12.STEAM MODELS – check to ensure air supply (80 psi [5.51 bar]) is on the dryer.

13.STEAM MODELS – check to ensure ALL steam shutoff valves are open.

14.STEAM MODELS – check steam damper operation.

15.Check basket (tumbler) bearing setscrews to ensure they are ALL tight.

113202 - 10

www.amdry.com

31

Image 35
Contents AD-115ES Installation Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Safety PrecautionsStandard Specifications SPECIFICATIONS/COMPONENT IdentificationSpecifications Gas, Electric, and Steam Component Identification 113202 Location Requirements Installation ProceduresUnpacking and Setting UP American Dryer Corp 113202 This Exhaust Duct Transition Piece Must be Installed First Fresh AIR Supply Requirements Dryer Enclosure RequirementsGeneral Exhaust Ductwork Information Exhaust RequirementsAmerican Dryer Corp 113202 Outside Ductwork Protection American Dryer Corp 113202 Electrical Information Reversing, 3ø Motor Gas and Steam Reversing, 3ø Motor Electric American Dryer Corp 113202 GAS Information Type of GAS Type of GAS American Dryer Corp 113202 Steam Information Operating Steam PressureCompressed Air Supply Air Pressure Steam Damper System113202 Before YOU Start Check Local Codes and Permits Water Information113202 Typical Water Supply Preparation for Operation and START-UP Preoperational Test Basket Tumbler Coating Preoperational Instructions Dual Timer DryersShutdown Instructions Reversing Timer SPIN/DWELL AdjustmentsParts SERVICE/PARTS InformationService Returning Warranty Parts Warranty InformationReturning Warranty Cards WarrantyAmerican Dryer Corp 113202 Suggested Cleaning Schedule Routine MaintenanceCleaning Lubrication AdjustmentsData Label Information Procedure for Functional Check Replacement Components 113202 Dual Timer Manual Reset Burner HI-LIMIT InstructionsPhase 113202 ADC Part No 10 12/10/08