d.Shutoff valves for each dryer should be installed in the supply, return, and drip trap return lines. This will allow the dryer to be isolated from the supply and return mains if the dryer needs maintenance work.
e.Install an inverted bucket steam trap and check valve for each unit at least
f.A
g.Dryers with optional solenoid valve must be mounted with coil positioned directly above the valve body.
h.The supply and return lines should be insulated. This will save energy and provide safety for the operator and maintenance personnel.
i.Water pockets in the supply line, caused by low points, will provide wet steam to the coil, possibly causing coil damage. ALL horizontal runs of steam supply piping should be pitched
STEAM DAMPER SYSTEM
4.Steam Damper Air System Connections
The dryer is manufactured with a pneumatic (piston) damper system, which requires an external supply of compressed air. The air connection is made to the steam damper solenoid valve, which is located at the rear inner top area of the dryer just above the electric service relay box.
a. Air Requirements
Compressed Air Supply | Air Pressure | |
Normal | 80 psi | 5.51 bar |
Minimum Supply | 70 psi | 4.82 bar |
Maximum Supply | 90 psi | 6.21 bar |
Shaded areas are stated in metric equivalents
26 | American Dryer Corp. | 113202 - 10 |