2.Technical Data
a. Gas Specifications
| TYPE OF GAS |
| ||
|
|
|
|
|
| NATURAL | LIQUID PROPANE | ||
|
|
|
|
|
Manifold Pressure* | 3.5 inches W.C. | 8.7 mb | 10.5 inches W.C. | 26.1 mb |
|
|
|
|
|
6.0 - 12.0 inches W.C. | 14.92 - 29.9 mb | 11.0 inches W.C. | 27.4 mb | |
|
|
|
|
|
Shaded areas are stated in metric equivalents
*Measured at the gas valve pressure tap when the gas valve is on.
b.Gas Connections:
Inlet connection
Inlet supply size
1)Natural Gas
Regulation is controlled by the dryer’s gas valve’s internal regulator. Incoming supply pressure must be consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches (29.9 mb) water column (W.C.) pressure.
2)Liquid Propane (L.P.) Gas
Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so that the gas pressure must be regulated upstream of the dryer. The pressure measured at each gas valve pressure tap must be a consistent 10.5 inches (26.1 mb) water column. There is no regulator or regulation provided in an L.P. dryer. The water column pressure must be regulated at the source (L.P. tank) or an external regulator must be added to each dryer.
|
|
| TYPE OF GAS |
| Liquid | ||||
|
|
|
|
|
|
|
|
| Propane |
|
|
| Natural |
|
| Liquid Propane | |||
Btu/hour | kcal/hr |
|
|
| Conversion Kit | ||||
|
|
|
|
|
|
| |||
Rating | Rating | Qty. | D.M.S.* |
| Part No. | Qty. | D.M.S.* | Part No. | Part Number |
|
|
|
|
|
|
|
|
|
|
550,000 | 138,600 | 4 | #2 |
| 140839 | 4 | #29 | 140820 | 880978 |
|
|
|
|
|
|
|
|
|
|
Shaded area is stated in metric equivalent
* Drill Measurement Size (D.M.S.) equivalents are as follows:
Natural Gas | #2 = 0.2210” | (5.6134 mm). |
Liquid Propane Gas | #29 = 0.1360” | (3.4544 mm). |
26