Amana Automatic Dryer installation instructions Electric and GAS Dryer

Page 5

 

 

ELECTRIC AND GAS DRYER

 

 

 

 

 

 

 

 

Weather Hood Type

 

 

 

 

 

 

 

Recommended

Use only for short run installation

 

 

 

 

 

 

4”(10,16 cm)

 

 

2 1/2”(6,35 cm)

 

 

 

 

 

No. of 90°

Rigid

Metallic Flexible*

Rigid

Metallic Flexible*

elbows

0

24.4 m (80 ft.)

12.4 m (41 ft.)

22.6 m (74 ft.)

10.1 m (33 ft.)

1

20.7 m (68 ft.)

11.2 m (37 ft.)

18.9 m (62 ft.)

8.8 m (29 ft.)

2

17.4 m (57 ft.)

10.1 m (33 ft.)

15.5 m (51 ft.)

7.6 m (25 ft.)

3

14.3m (47 ft.)

9.0 m (29 ft.)

12.5 m (41 ft.)

6.5 m (21 ft.)

 

 

 

 

 

*Do not use non metallic flexible duct.

Exhaust systems longer than recommended can extend drying times, affect machine operation and may collect lint.

The exhaust duct should end with an exhaust hood with a swing out damper to prevent back drafts and entry of wildlife. Never use an exhaust hood with a magnetic damper.

The hood should have at least 12 inches (30.5 cm) of clearance between the bottom of the hood and the ground or other obstruction. The hood opening should point down.

Never install a screen over the exhaust outlet.

When possible, do not exhaust the dryer directly into a window well in order to avoid lint build- up. Do not exhaust under a house or porch.

If exhaust ductwork must run through an unheated area, the duct should be insulated and slope slightly down towards the exhaust hood to reduce condensation and lint build-up.

Inspect and clean the interior or the exhaust system at least once a year. Disconnect electrical service prior to cleaning.

Frequently check to be sure the exhaust hood damper opens and closes freely.

If new dryer is installed into an existing exhaust system you must be sure:

The exhaust system meets all local, state and national codes.

That plastic flexible duct is not used.

Inspect and clean all lint accumulation from the interior of the existing duct.

The duct is not kinked or crushed.

The exhaust hood damper opens and closes freely.

The static pressure in any exhaust system must not exceed 0.83 inches of water column, or be less than 0.

This can be measured with the dryer running with a manometer at the point where the exhaust duct connects to the dryer. A no heat setting should be used.

The dryer tumbler should be empty and the lint filter clean.

5

Image 5
Contents DC68-02033C W10161760 Tools needed for installation Cabinet DimensionsItems Provided Electric Dryer Gas Dryer OnlyMobile Home Installation Important to InstallerAlcove or Closet Installation Never USE Plastic or Nonmetal Flexible Duct ExhaustingDucting Requirements Electric and GAS Dryer GAS Ignition GAS RequirementsGrounding Electrical RequirementsGAS Models Electric ModelsGAS Models U.S. and Canada Electrical ConnectionsElectric Models U.S. Only Extension CordLeaks Use plastic flexible exhaust materialModels Export Models Wire System ConnectionsHousehold Installation Accessories Final Installation Check ListAdditional Instructions for Export Models Wire System ConnectionsExport Electric Models Export GAS ModelsDoor Reversal Articles Fournis DimensionsOutils nécessaires à linstallation Installation Dans UNE Alcôve OU UN Placard Avis Important À LinstallateurInstallation Dans UNE Maison Mobile AvertissementExigences Relatives AUX Conduits Dévacuation ÉvacuationAux États-Unis Au CanadaSécheuses Électriques ET À GAZ Allumage AU GAZ Exigences Relatives AU GAZMise À LA Terre Exigences ÉlectriquesModèles À GAZ Modèles ÉlectriquesModèles Électriques États-Unis seulement Connexions ÉlectriquesModèles À GAZ États-Unis et Canada Remarque Il faut utiliser un serre-câble Modèles AméricainsModèles Destinés À Lexportation Connexions À UN Circuit À Trois ConducteursConnexions À UN Circuit À Quatre Conducteurs Accessoires Pour Installation Dans UNE Maison Liste DE Contrôle DE Linstallation FinaleModèles À GAZ Destinés À Lexportation Modèles Électriques Destinés À LexportationConnexions À UN Circuit À Deux Conducteurs Inversion de la porte Herramientas necesarias para la instalación Dimensiones DEL GabineteInstalación EN UN Armario O EN UN Hueco Importante Para EL InstaladorInstalación EN UNA Casa Rodante AdvertenciaNunca Utilice Conductos Flexibles Plásticos O no Metálicos EscapeRequisitos DEL Conducto Secadoras Eléctricas Y DEL GAS De encendido continuo Encendido DEL GASInstrucciones DE Instalación DE LA Commonwealth of MassachusettsPuesta a Tierra Requisitos EléctricosModelos DE GAS Modelos EléctricosModelos DE GAS EE.UU. y Canadá Conexiones EléctricasModelos Eléctricos Sólo para EE.UU Utilice UN Cable AlargadorNota Debe utilizarse un relevador de tensión Modelos EstadounidensesModelos DE Exportación Conexiones DEL Sistema DE 3 CablesConexiones DEL Sistema DE 4 Cables Accesorios DE Instalación EN EL Hogar Lista DE Verificación Final DE LA InstalaciónModelos Eléctricos DE Exportación Instrucciones Adicionales Para Modelos DE ExportaciónConexiones DEL Sistema DE 2 Cables Modelos DE GAS DE ExportaciónInversión de la puerta