2.Electrical Service Specifications
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.
B.Circuit breakers are
C.Circuit breakers for
SERVICE |
| WIRE | APPROX. | MINIMUM | FUSING | CIRCUIT | ||
PHASE | AMP DRAW |
| ||||||
Dual Element | ||||||||
VOLTAGE | SERVICE | WIRE SIZE | BREAKER | |||||
|
|
| 60 Hz | 50 Hz |
| Time Delay |
| |
208 | 3ø | 3 | 14.5 | * | 20 | 20 | ||
240 | 3ø | 3 | 14.6 | 16.4 | * |
| ||
380 | 3ø | 4** | 8.7 | * | 15 | 15 | ||
400 | 3ø | 4** | 8.5 | * | 15 | 15 | ||
416 | 3ø | 4** | 8.4 | * | 15 | 15 | ||
460/480 | 3ø | 3 | 7.8 | * | 15 | 15 | ||
575 | 3ø | 3 | 5.8 | * | 15 | 15 |
*AWG Stranded Wire Type...size wire as per National Electrical Code or local codes. (Motor lead wire is recommended.)
**
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the left side panel behind top/access control door. In the case of 208 VAC or 230 VAC, the supply voltage must match the electric service specifications of the data label exactly.
WARNING: 208 VAC AND 230 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.
IMPORTANT: 380, 400, and 416 Volt dryers are built