S.Dryer operates but is taking too long to dry...
1.Exhaust ductwork run too long or is undersized...back pressure must be no less than 0 and cannot exceed 0.3 inches (0.74 mb) water column (W.C.).
2.Restriction in exhaust ductwork...
a.Customer furnished exhaust back draft damper is sticking partially closed.
b.Restriction in exhaust ductwork...check ductwork from dryer ALL the way to the outdoors.
3.Low and/or inconsistent gas pressure (for Gas Models Only).
4.Insufficient
5.Poor air or gas mixture at burner...yellow or poor flame pattern; adjust gas burner air adjustment shutters (for Gas Models Only).
6.Lint screen is not being cleaned on a regular basis or often enough.
7.Extractors (washers) are not performing properly.
8.Sail switch is fluttering...restriction in exhaust ductwork (for Gas Models Only).
9.Failed microprocessor controller (computer)...temperature calibration is inaccurate.
10.Failed microprocessor temperature sensor calibration is inaccurate.
11.Failed oven
12.Steam damper system is not functioning properly (for Steam Models Only)...
a.Steam damper sticking closed.
b.Leak in the pneumatic system.
c.Flow control incorrectly set.
T.Condensation on main door glass...
1.Too long, undersized, or improperly installed ductwork.
2.Dryer connected to common exhaust duct with another dryer and no back draft damper was installed in customer furnished ductwork.
3.Customer furnished back draft damper in ductwork is sticking in partially closed position.
53