ADE-115ES (60 Kw Electric Oven) Reversing, 3ø Motor
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.
B.Circuit breakers are
C.Circuit breakers for
OVEN SIZE | SERVICE |
| WIRE | APPROX. | MINIMUM | FUSING | CIRCUIT | ||
PHASE | AMP DRAW | ||||||||
| |||||||||
(Kw) | VOLTAGE | SERVICE |
|
| WIRE SIZE |
| BREAKER | ||
60 Hz | 50 Hz | Dual Element | |||||||
|
|
|
|
| Time Delay |
| |||
|
|
|
|
|
|
|
| ||
60 | 208 | 3ø | 3 | 181 | * | 250 | 250 | ||
60 | 240 | 3ø | 3 | 159 | 161 | * | 200 | 200 | |
60 | 380 | 3ø | 4** | 100 | * | 125 | 125 | ||
60 | 400 | 3ø | 4** | 95 | * | 125 | 125 | ||
60 | 416 | 3ø | 4** | 92 | * | 125 | 125 | ||
60 | 460 | 3ø | 3 | 83 |
| * | 125 | 125 | |
60 | 480 | 3ø | 3 | 80 |
| * | 100 | 100 | |
60 | 575 | 3ø | 3 | 66 |
| * | 100 | 100 |
*AWG Stranded Wire Type...size wire as per National Electrical Code or local codes. (Motor lead wire is recommended.)
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the left side panel behind top/access control door. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.
WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer components due to improper voltage connections will automatically VOID THE WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or obligation.
IMPORTANT: 380, 400, and 416 Volt dryers are built