Schneider Electric VW3 A3 303 user manual Communication scanner, Rdy Net, COM. Scanner Input

Page 18

6. Configuration

6. 3. Communication scanner

The communication scanner enables all the application-relevant parameters to be grouped in 2 consecutive word tables so that single read and write operations may be performed. It is even possible to perform a single transaction using the "Read/Write Multiple Registers" (23 = 16#17) function.

The 8 output variables are assigned using the 8 [Scan.Outp address] (nCAp) parameters. They are configured using the graphic display terminal via the [1.9 - COMMUNICATION] (COM-)menu, [COM. SCANNER OUTPUT] (OCS-)submenu.

The 8 input variables are assigned using the 8 [Scan. INp address] (nMAp) parameters. They are configured using the graphic display terminal via the [1.9 - COMMUNICATION] (COM-)menu, [COM. SCANNER INPUT] (ICS-)submenu.

Enter the logic address of the parameter (see the Parameters Manual).

If a [Scan.Outp address] (nCAp) or [Scan. INp address] (nMAp) parameter equals zero, the corresponding variable is not used by the drive.

These 16 assignment parameters are described in the tables below:

Configuration parameter name

Default assignment of the output variable

[Scan. Out1 address] (nCA1)

Control word (CMd)

 

 

[Scan. Out2 address] (nCA2)

Speed reference (LFrd)

 

 

[Scan. Out3 address] (nCA3)

Not used

 

 

[Scan. Out4 address] (nCA4)

Not used

 

 

[Scan. Out5 address] (nCA5)

Not used

 

 

[Scan. Out6 address] (nCA6)

Not used

 

 

[Scan. Out7 address] (nCA7)

Not used

 

 

[Scan. Out8 address] (nCA8)

Not used

 

 

Configuration parameter name

Default assignment of the input variable

[Scan. IN1 address] (nMA1)

Status word (EtA)

 

 

[Scan. IN2 address] (nMA2)

Output speed (rFrd)

 

 

[Scan. IN3 address] (nMA3)

Not used

 

 

[Scan. IN4 address] (nMA4)

Not used

 

 

[Scan. IN5 address] (nMA5)

Not used

 

 

[Scan. IN6 address] (nMA6)

Not used

 

 

[Scan. IN7 address] (nMA7)

Not used

 

 

[Scan. IN8 address] (nMA8)

Not used

 

 

Example of configuration via the graphic display terminal:

 

RDY

 

NET

 

+0.00Hz

0A

 

 

 

 

 

 

 

COM. SCANNER INPUT

 

 

 

 

 

 

 

Scan. IN1 address

:

 

 

3201

Scan. IN2 address

:

 

 

8604

Scan. IN3 address

:

 

 

0

Scan. IN4 address

:

 

 

0

Scan. IN5 address

:

 

 

0

 

 

 

 

 

 

 

 

 

 

Code

 

 

 

 

Quick

 

 

 

 

 

 

 

 

 

 

Scan. IN6 address

:

 

 

0

Scan. IN7 address

:

 

 

0

Scan. IN8 address

:

 

 

0

 

RDY

 

NET

 

+0.00Hz

0A

 

 

 

 

 

 

 

COM. SCANNER OUTPUT

 

 

 

 

 

 

 

Scan. Out1 address

:

 

 

8501

Scan. Out2 address

:

 

 

8602

Scan. Out3 address

:

 

 

0

Scan. Out4 address

:

 

 

0

Scan. Out5 address

:

 

 

0

 

 

 

 

 

 

 

 

Code

 

 

 

Quick

 

 

 

 

 

 

 

 

 

 

Scan. Out6 address

:

 

 

0

Scan. Out7 address

:

 

 

0

Scan. Out8 address

:

 

 

0

Note:

Any modification to parameters [Scan.Outp address] (nCAp) or [Scan. INp address] (nMAp) must be made with the motor stopped. The master PLC program should be updated to take account of this modification.

18

Image 18
Contents Altivar Contents Before you begin Electric shock will result in death or serious injuryProgramming Manual Installation ManualDocumentation structure Communication Parameters ManualIntroduction PresentationNotation Receipt Hardware setupInstalling the card in the drive Hardware descriptionSwitch coding Choosing polarizationCoding the address Address 1234Connecting to the bus Wiring recommendationsModbus RS485 standard Connection via RJ45 wiring system Connection accessoriesConnection cables TWD XCA RJ030 Connection cables for the masterType of master Master interface Description Catalog number TSX SCP CMRS485 double shielded twisted pair Connection via junction boxesDescription Catalog Number Subscriber socket CablesTSX CSA500 TSX P ACCConfiguration Communication parametersControl via Modbus or the terminals in I/O profile Control CommandControl via Modbus in I/O profile Parameter Value CommentControl via Modbus in Drivecom profile Control via Modbus or the terminals in Drivecom profileConfiguration RDY NET Example of configuration via the graphic display terminalCommunication scanner COM. Scanner InputCommunication faults COM. Fault ManagementFormat CONFIG. COMM. MAPMonitored parameters Format Range Terminal displayLEDs DiagnosticsChecking the address Green RUN Red ERR Meaning Corrective actionCOM. Scanner Input MAP RUN NETCommunication MAP COM Scan Output MAP CMD. Word ImageInput variable Scanner parameter Output variable Scanner parameterCOM Scan Output MAP Communication fault Card faultModbus protocol PrincipleSlave Slave j Slave k Modes RTU modeAscii mode Slave address Function code DataModbus functions available Read Holding/Input Registers 3/4Code Modbus name Description Broadcast Size of data Write Single Register Diagnostics Get Comm Event Counter 11 = 16#0B Write Multiple Registers 16 = 16#10Read/Write Multiple Registers 23 = 16#17 Read Device Identification 43 = 16#2B MachineExample of positive response MEIOutput variables Logic address Default assignment Input variables Logic address Default assignmentCode Modbus name Description Size of data Input variable address Logic address Default value Parameter Logic ReadParameter Logic Input monitoring Output controlParameter assigned Value Parameter assignedCode Error code Exception responsesResponse Read non-existent or protected parameters Logic address Parameter ValueAppendix RS485 standardModbus 2-wire standard schematic MasterModbus 4-wire standard schematic Uni-Telway schematic Wire Jbus schematic Type of trunk cable Cable with 1 shielded twisted pairCreating a Modbus bus using non-standard equipment Different scenariosRecommendations Calculating the polarization ExampleContact no. Signal RS485 schematic for the cardCard connector pinout SUB-DAtv71ModbusJbusENV1 2005-05