Schneider Electric VW3 A3 303 user manual Control Command, Control via Modbus in I/O profile

Page 15

6. Configuration

6. 2. Control - Command

Numerous configurations are possible. For more information, refer to the Programming Manual and the Parameters Manual. The following configurations are just some of the possibilities available.

bControl via Modbus in I/O profile

The command and reference come from Modbus.

The command is in I/O profile.

Configure the following parameters:

Parameter

Value

Comment

Profile

I/O profile

The run command is simply obtained by bit 0 of the control word.

 

 

 

Reference 1 configuration

Network card

The reference comes from Modbus.

 

 

 

Command 1 configuration

Network card

The command comes from Modbus.

 

 

 

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[I/O profile] (IO)

 

 

 

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

 

 

 

[Cmd channel 1] (Cd1)

[Com. card] (nEt)

 

 

 

bControl via Modbus or the terminals in I/O profile

Both the command and reference come from Modbus or the terminals. Input LI5 at the terminals is used to switch between Modbus and the terminals.

The command is in I/O profile.

Configure the following parameters:

Parameter

Value

Comment

Profile

I/O profile

The run command is simply obtained by bit 0 of the control word.

 

 

 

Reference 1 configuration

Network card

Reference 1 comes from Modbus.

 

 

 

Reference 1B configuration

Analog input 1 on the terminals

Reference 1B comes from input AI1 on the terminals.

 

 

 

Reference switching

Input LI5

Input LI5 switches the reference (1 1B).

 

 

 

Command 1 configuration

Network card

Command 1 comes from Modbus.

 

 

 

Command 2 configuration

Terminals

Command 2 comes from the terminals.

 

 

 

Command switching

Input LI5

Input LI5 switches the command.

 

 

 

Note: Reference 1B is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference (summing, PID, etc) are inhibited.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6

- COMMAND] (CtL-)

[Profile] (CHCF)

[I/O profile] (IO)

 

 

 

 

 

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

 

 

 

 

 

[Cmd channel 1] (Cd1)

[Com. card] (nEt)

 

 

 

 

 

 

[Cmd channel 2] (Cd2)

[Terminals] (tEr)

 

 

 

 

 

 

[Cmd switching] (CCS)

[LI5] (LI5)

 

 

 

 

[1.7

APPLICATION FUNCT.] (FUn-)

[Ref.1B channel] (Fr1b)

[Ref. AI1] (AI1)

[REFERENCE SWITCH.]

 

 

[Ref 1B switching] (rCb)

[LI5] (LI5)

 

 

 

 

 

 

15

Image 15
Contents Altivar Contents Electric shock will result in death or serious injury Before you beginCommunication Parameters Manual Installation ManualDocumentation structure Programming ManualIntroduction PresentationNotation Hardware description Hardware setupInstalling the card in the drive ReceiptSwitch coding Choosing polarizationCoding the address 1234 AddressConnecting to the bus Wiring recommendationsModbus RS485 standard Connection via RJ45 wiring system Connection accessoriesConnection cables TSX SCP CM Connection cables for the masterType of master Master interface Description Catalog number TWD XCA RJ030Cables Connection via junction boxesDescription Catalog Number Subscriber socket RS485 double shielded twisted pairTSX P ACC TSX CSA500Communication parameters ConfigurationParameter Value Comment Control CommandControl via Modbus in I/O profile Control via Modbus or the terminals in I/O profileControl via Modbus or the terminals in Drivecom profile Control via Modbus in Drivecom profileConfiguration COM. Scanner Input Example of configuration via the graphic display terminalCommunication scanner RDY NETCOM. Fault Management Communication faultsFormat Range Terminal display CONFIG. COMM. MAPMonitored parameters FormatGreen RUN Red ERR Meaning Corrective action DiagnosticsChecking the address LEDsCOM Scan Output MAP CMD. Word Image RUN NETCommunication MAP COM. Scanner Input MAPInput variable Scanner parameter Output variable Scanner parameterCOM Scan Output MAP Card fault Communication faultModbus protocol PrincipleSlave Slave j Slave k Slave address Function code Data RTU modeAscii mode ModesModbus functions available Read Holding/Input Registers 3/4Code Modbus name Description Broadcast Size of data Write Single Register Diagnostics Write Multiple Registers 16 = 16#10 Get Comm Event Counter 11 = 16#0BRead/Write Multiple Registers 23 = 16#17 Machine Read Device Identification 43 = 16#2BMEI Example of positive responseOutput variables Logic address Default assignment Input variables Logic address Default assignmentCode Modbus name Description Size of data Input variable address Logic address Default value Parameter Logic ReadParameter Logic Value Parameter assigned Output controlParameter assigned Input monitoringCode Error code Exception responsesResponse Logic address Parameter Value Read non-existent or protected parametersRS485 standard AppendixMaster Modbus 2-wire standard schematicModbus 4-wire standard schematic Uni-Telway schematic Type of trunk cable Cable with 1 shielded twisted pair Wire Jbus schematicCreating a Modbus bus using non-standard equipment Different scenariosRecommendations Example Calculating the polarizationSUB-D RS485 schematic for the cardCard connector pinout Contact no. SignalAtv71ModbusJbusENV1 2005-05