9. Appendix
9. 2. Modbus 2-wire standard schematic
The standard schematic corresponds to the Modbus specification published in 2002 on www.modbus.org (Modbus_over_serial_line_V1.pdf, Nov 2002) and, in particular, to the
The Modbus card (VW3 A3 303) conforms to this specification.
Schematic diagram:
Master |
|
|
R | G | 5 V |
| ||
|
| 650 Ω |
650 Ω |
|
|
| 0 V |
|
D1 |
|
|
120 Ω |
| 120 Ω |
1n F |
| 1n F |
D0 |
|
|
Common |
|
|
R
G
Slave 1
R
G
Slave n
Type of trunk cable | Shielded cable with 1 twisted pair and at least a 3rd conductor |
Maximum length of bus | 1000 m at 19200 bps with the Telemecanique TSX CSAp00 cable |
|
|
Maximum number of stations (without | 32 stations, i.e., 31 slaves |
repeater) |
|
Maximum length of tap links | • 20 m for one tap link |
| • 40 m divided by the number of tap links on a multiple junction box |
Bus polarization | • One 450 to 650 Ω |
| • One 450 to 650 Ω |
| recommended) |
| This polarization is recommended for the master. |
Line termination | One 120 Ω 0.25 W resistor in series with a 1nF 10 V capacitor |
|
|
Common polarity | Yes (Common), connected to the protective ground at one or more points on the bus |
|
|
40