Schneider Electric VW3 A3 303 Input variable Scanner parameter, Output variable Scanner parameter

Page 23

7. Diagnostics

7. 4. Communication scanner

On the graphic display terminal, in the [1.2 - MONITORING] (SUP-)menu ([COMMUNICATION MAP] (CMM-)submenu):

-The [COM. SCANNER INPUT MAP] (ISA-)submenu is used to display the value of the 8 communication scanner input variables [Com Scan Inp val.] (NMp).

-The [COM SCAN OUTPUT MAP] (OSA-)submenu is used to display the value of the 8 communication scanner output variables [Com Scan Outp val.] (NCp).

Input variable

Scanner parameter

No. 1

[Com Scan In1 val.] (NM1)

No. 2

[Com Scan In2 val.] (NM2)

No. 3

[Com Scan In3 val.] (NM3)

No. 4

[Com Scan In4 val.] (NM4)

No. 5

[Com Scan In5 val.] (NM5)

No. 6

[Com Scan In6 val.] (NM6)

No. 7

[Com Scan In7 val.] (NM7)

No. 8

[Com Scan In8 val.] (NM8)

Output variable

Scanner parameter

No. 1

[Com Scan Out1 val.] (NC1)

No. 2

[Com Scan Out2 val.] (NC2)

No. 3

[Com Scan Out3 val.] (NC3)

No. 4

[Com Scan Out4 val.] (NC4)

No. 5

[Com Scan Out5 val.] (NC5)

No. 6

[Com Scan Out6 val.] (NC6)

No. 7

[Com Scan Out7 val.] (NC7)

No. 8

[Com Scan Out8 val.] (NC8)

Configuration of these variables is described in the "Configuration" section.

Example of communication scanner display on the graphic display terminal:

RUN

 

NET

 

+50.00Hz

80A

 

 

 

 

 

 

 

COM. SCANNER INPUT MAP

 

 

 

 

 

 

 

Com Scan In1 val.

:

 

 

34359

Com Scan In2 val.

:

 

 

600

Com Scan In3 val.

:

 

 

0

Com Scan In4 val.

:

 

 

0

Com Scan In5 val.

:

 

 

0

 

 

 

 

 

 

 

Code

 

 

 

Quick

 

 

 

 

 

 

 

 

 

Com Scan In6 val.

:

 

 

0

Com Scan In7 val.

:

 

 

0

Com Scan In8 val.

:

 

 

0

RUN

 

NET

 

+50.00Hz

80A

 

 

 

 

 

 

 

COM SCAN OUTPUT MAP

 

 

 

 

 

 

 

Com Scan Out1 val.

:

 

 

15

Com Scan Out2 val.

:

 

 

598

Com Scan Out3 val.

:

 

 

0

Com Scan Out4 val.

:

 

 

0

Com Scan Out5 val.

:

 

 

0

 

 

 

 

 

 

 

Code

 

 

 

Quick

 

 

 

 

 

 

 

 

 

Com Scan Out6 val.

:

 

 

0

Com Scan Out7 val.

:

 

 

0

Com Scan Out8 val.

:

 

 

0

In this example, only the first two variables have been configured (default assignment).

[Com Scan In1 val.]

= [34343]

Status word = 34359 = 16#8637

V

Drivecom "Operation enabled" state,

 

 

 

 

reverse operation, speed reached

[Com Scan In2 val.]

= [600]

Output speed = 600

V

600 rpm

[Com Scan Out1 val.]

= [15]

Control word = 15 = 16#000F

V

"Enable operation" (Run) command

[Com Scan Out2 val.]

= [598]

Speed reference = 600

V

598 rpm

23

Image 23
Contents Altivar Contents Electric shock will result in death or serious injury Before you beginCommunication Parameters Manual Installation ManualDocumentation structure Programming ManualNotation IntroductionPresentation Hardware description Hardware setupInstalling the card in the drive ReceiptCoding the address Switch codingChoosing polarization 1234 AddressModbus RS485 standard Connecting to the busWiring recommendations Connection cables Connection via RJ45 wiring systemConnection accessories TSX SCP CM Connection cables for the masterType of master Master interface Description Catalog number TWD XCA RJ030Cables Connection via junction boxesDescription Catalog Number Subscriber socket RS485 double shielded twisted pairTSX P ACC TSX CSA500Communication parameters ConfigurationParameter Value Comment Control CommandControl via Modbus in I/O profile Control via Modbus or the terminals in I/O profileControl via Modbus or the terminals in Drivecom profile Control via Modbus in Drivecom profileConfiguration COM. Scanner Input Example of configuration via the graphic display terminalCommunication scanner RDY NETCOM. Fault Management Communication faultsFormat Range Terminal display CONFIG. COMM. MAPMonitored parameters FormatGreen RUN Red ERR Meaning Corrective action DiagnosticsChecking the address LEDsCOM Scan Output MAP CMD. Word Image RUN NETCommunication MAP COM. Scanner Input MAPCOM Scan Output MAP Input variable Scanner parameterOutput variable Scanner parameter Card fault Communication faultSlave Slave j Slave k Modbus protocolPrinciple Slave address Function code Data RTU modeAscii mode ModesCode Modbus name Description Broadcast Size of data Modbus functions availableRead Holding/Input Registers 3/4 Write Single Register Diagnostics Write Multiple Registers 16 = 16#10 Get Comm Event Counter 11 = 16#0BRead/Write Multiple Registers 23 = 16#17 Machine Read Device Identification 43 = 16#2BMEI Example of positive responseCode Modbus name Description Size of data Output variables Logic address Default assignmentInput variables Logic address Default assignment Parameter Logic Input variable address Logic address Default valueParameter Logic Read Value Parameter assigned Output controlParameter assigned Input monitoringResponse Code Error codeException responses Logic address Parameter Value Read non-existent or protected parametersRS485 standard AppendixMaster Modbus 2-wire standard schematicModbus 4-wire standard schematic Uni-Telway schematic Type of trunk cable Cable with 1 shielded twisted pair Wire Jbus schematicRecommendations Creating a Modbus bus using non-standard equipmentDifferent scenarios Example Calculating the polarizationSUB-D RS485 schematic for the cardCard connector pinout Contact no. SignalAtv71ModbusJbusENV1 2005-05