6. Configuration
6. 5. Monitored parameters
It is possible to select up to 4 parameters to display their values in the [1.2 - MONITORING] menu ([COMMUNICATION MAP] submenu) on the graphic display terminal.
The selection is made via the [6 – MONITOR CONFIG.] menu ([6.3 - CONFIG. COMM. MAP] submenu).
Each parameter [Address 1 select] ... [Address 4 select] can be used to choose the logic address of the parameter. Select an address of zero to disable the function.
In the example given here, the monitored words are:
•Parameter 1 = Motor current (LCr): logic address 3204; signed decimal format
•Parameter 2 = Motor torque (Otr): logic address 3205; signed decimal format
•Parameter 3 = Last fault occurred (LFt): logic address 7121; hexadecimal format
•Disabled parameter: address 0; default format: hexadecimal format
One of the three display formats below can be assigned to each monitored word:
| RDY | NET |
| +0.00Hz | 0A | ||
|
| ||||||
| 6.3 CONFIG. COMM. MAP. | ||||||
|
|
|
|
| |||
Address 1 select | : |
|
| 3204 | |||
FORMAT 1 |
| : |
|
| Signed | ||
Address 2 select | : |
|
| 3205 | |||
FORMAT 2 |
| : |
|
| Signed | ||
Address 3 select | : |
|
| 7121 | |||
|
|
|
|
|
|
|
|
| Code |
|
|
|
| Quick |
|
|
|
|
|
|
|
|
|
FORMAT 3 |
| : |
|
| Hex | ||
Address 4 select | : |
|
| 0 | |||
FORMAT 4 |
| : |
|
| Hex |
Format | Range | Terminal display |
Hexadecimal | 0000 ... FFFF | [Hex] |
|
|
|
Signed decimal | [Signed] | |
|
|
|
Unsigned decimal | 0 ... 65,535 | [Unsigned] |
|
|
|
20