Schneider Electric VW3 A3 303 user manual Control via Modbus in Drivecom profile

Page 16

6. Configuration

bControl via Modbus in Drivecom profile

The command and reference come from Modbus.

The command is in Drivecom profile.

Configure the following parameters:

Parameter

Value

Comment

Profile

Drivecom profile not

The run commands are in Drivecom profile, the command and the reference

 

separate

come from the same channel.

Reference 1 configuration

Network card

The command comes from Modbus.

 

 

 

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[Not separ.] (SIM) (factory setting)

 

 

 

 

[Ref. 1] (Fr1)

[Com. card] (nEt)

 

 

 

bControl via Modbus or the terminals in Drivecom profile

Both the command and reference come from Modbus or the terminals. Input LI5 at the terminals is used to switch between Modbus and the terminals.

The command is in Drivecom profile.

Configure the following parameters:

Parameter

Value

Comment

Profile

Drivecom profile not separate

The run commands follow the Drivecom profile, and the command and

 

 

reference come from the same channel.

Reference 1 configuration

Network card

Reference 1 comes from Modbus.

 

 

 

Reference 2 configuration

Analog input 1 on the terminals

Reference 2 comes from input AI1 on the terminals.

 

 

 

Reference switching

Input LI5

Input LI5 switches the reference (1 2) and the command.

 

 

 

Caution: Reference 2 is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference (summing, PID, etc) are inhibited.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[Not separ.] (SIM)

 

 

 

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

 

 

 

[Ref.2 channel] (Fr2)

[Ref. AI1] (AI1)

 

 

 

 

[Ref. 2 switching] (rFC)

[LI5] (LI5)

 

 

 

16

Image 16
Contents Altivar Contents Before you begin Electric shock will result in death or serious injuryInstallation Manual Documentation structureProgramming Manual Communication Parameters ManualPresentation IntroductionNotation Hardware setup Installing the card in the driveReceipt Hardware descriptionChoosing polarization Switch codingCoding the address Address 1234Wiring recommendations Connecting to the busModbus RS485 standard Connection accessories Connection via RJ45 wiring systemConnection cables Connection cables for the master Type of master Master interface Description Catalog numberTWD XCA RJ030 TSX SCP CMConnection via junction boxes Description Catalog Number Subscriber socketRS485 double shielded twisted pair CablesTSX CSA500 TSX P ACCConfiguration Communication parametersControl Command Control via Modbus in I/O profileControl via Modbus or the terminals in I/O profile Parameter Value CommentControl via Modbus in Drivecom profile Control via Modbus or the terminals in Drivecom profileConfiguration Example of configuration via the graphic display terminal Communication scannerRDY NET COM. Scanner InputCommunication faults COM. Fault ManagementCONFIG. COMM. MAP Monitored parametersFormat Format Range Terminal displayDiagnostics Checking the addressLEDs Green RUN Red ERR Meaning Corrective actionRUN NET Communication MAPCOM. Scanner Input MAP COM Scan Output MAP CMD. Word ImageOutput variable Scanner parameter Input variable Scanner parameterCOM Scan Output MAP Communication fault Card faultPrinciple Modbus protocolSlave Slave j Slave k RTU mode Ascii modeModes Slave address Function code DataRead Holding/Input Registers 3/4 Modbus functions availableCode Modbus name Description Broadcast Size of data Write Single Register Diagnostics Get Comm Event Counter 11 = 16#0B Write Multiple Registers 16 = 16#10Read/Write Multiple Registers 23 = 16#17 Read Device Identification 43 = 16#2B MachineExample of positive response MEIInput variables Logic address Default assignment Output variables Logic address Default assignmentCode Modbus name Description Size of data Parameter Logic Read Input variable address Logic address Default valueParameter Logic Output control Parameter assignedInput monitoring Value Parameter assignedException responses Code Error codeResponse Read non-existent or protected parameters Logic address Parameter ValueAppendix RS485 standardModbus 2-wire standard schematic MasterModbus 4-wire standard schematic Uni-Telway schematic Wire Jbus schematic Type of trunk cable Cable with 1 shielded twisted pairDifferent scenarios Creating a Modbus bus using non-standard equipmentRecommendations Calculating the polarization ExampleRS485 schematic for the card Card connector pinoutContact no. Signal SUB-DAtv71ModbusJbusENV1 2005-05