Schneider Electric VW3 A3 303 user manual Calculating the polarization, Example

Page 45

9. Appendix

bCalculating the polarization

MPrinciple

You must ensure that the equivalent bus resistance is between 162 Ω and 650 Ω.

The equivalent bus resistance (Re) depends on the polarization resistance of the slaves (Rs) and the master (Rm):

1 1 1 1

-------= --------- + ---------+ --------- + Re Rm Rs1 Rs2

If Re is too low, reduce the number of slaves.

If Re is too high, adapt the master’s polarization (if possible) or add polarization resistors (Rp).

1

=

1

1

1

1

 

 

-------

-------

+ ---------

+ --------- + --------- +

 

Re

 

Rp

Rm

Rs1

Rs2

 

 

 

 

 

 

 

Master

 

 

 

 

 

 

 

R

G

5 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rm

5 V

 

 

 

 

Rm

 

 

 

Rp

 

 

 

 

 

0 V

 

 

 

D1

 

 

 

 

 

 

 

 

120 Ω

 

 

 

 

 

 

 

 

1 nF

 

 

 

 

 

 

 

 

D0

 

 

 

 

 

 

 

 

Common

 

 

 

 

 

 

 

5 V

 

 

 

 

 

 

 

Rp

Rs1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rs1 0 V

0 V

R

G

R

G

Slave 1

Slave n

Example 1

If the master has 470 Ω polarization and all the slaves have 4.7 kΩ polarization, a maximum of 18 slaves can be connected.

Rm = 470 Ω

Rs = 4.7 kΩ

A/Re = 1/470 + 18 x 1/4700 i.e., Re = 168 Ω

Example 2

If the bus polarization Rp is 470 Ω (installed in the master) and 2 slaves have 4.7 Ω polarization, the equivalent polarization is: 1/Re = 1/470 + 1/4700 + 1/4700

i.e., Re = 1/ (1/470 + 1/4700 + 1/4700) and therefore Re = 390 Ω

390 Ω is between 162 Ω and 650 Ω, and the schematic is correct.

For an ideal equivalent polarization (650 Ω), the master’s polarization can be adapted so that: 1/650 = 1/Rm + 1/4700 + 1/4700

i.e., Rm = 1/(1/650 - 1/4700 - 1/4700) and therefore Rm = 587 Ω

45

Image 45
Contents Altivar Contents Electric shock will result in death or serious injury Before you beginDocumentation structure Installation ManualProgramming Manual Communication Parameters ManualIntroduction PresentationNotation Installing the card in the drive Hardware setupReceipt Hardware descriptionSwitch coding Choosing polarizationCoding the address 1234 AddressConnecting to the bus Wiring recommendationsModbus RS485 standard Connection via RJ45 wiring system Connection accessoriesConnection cables Type of master Master interface Description Catalog number Connection cables for the masterTWD XCA RJ030 TSX SCP CMDescription Catalog Number Subscriber socket Connection via junction boxesRS485 double shielded twisted pair CablesTSX P ACC TSX CSA500Communication parameters ConfigurationControl via Modbus in I/O profile Control CommandControl via Modbus or the terminals in I/O profile Parameter Value CommentControl via Modbus or the terminals in Drivecom profile Control via Modbus in Drivecom profileConfiguration Communication scanner Example of configuration via the graphic display terminalRDY NET COM. Scanner InputCOM. Fault Management Communication faultsMonitored parameters CONFIG. COMM. MAPFormat Format Range Terminal displayChecking the address DiagnosticsLEDs Green RUN Red ERR Meaning Corrective actionCommunication MAP RUN NETCOM. Scanner Input MAP COM Scan Output MAP CMD. Word ImageInput variable Scanner parameter Output variable Scanner parameterCOM Scan Output MAP Card fault Communication faultModbus protocol PrincipleSlave Slave j Slave k Ascii mode RTU modeModes Slave address Function code DataModbus functions available Read Holding/Input Registers 3/4Code Modbus name Description Broadcast Size of data Write Single Register Diagnostics Write Multiple Registers 16 = 16#10 Get Comm Event Counter 11 = 16#0BRead/Write Multiple Registers 23 = 16#17 Machine Read Device Identification 43 = 16#2BMEI Example of positive responseOutput variables Logic address Default assignment Input variables Logic address Default assignmentCode Modbus name Description Size of data Input variable address Logic address Default value Parameter Logic ReadParameter Logic Parameter assigned Output controlInput monitoring Value Parameter assignedCode Error code Exception responsesResponse Logic address Parameter Value Read non-existent or protected parametersRS485 standard AppendixMaster Modbus 2-wire standard schematicModbus 4-wire standard schematic Uni-Telway schematic Type of trunk cable Cable with 1 shielded twisted pair Wire Jbus schematicCreating a Modbus bus using non-standard equipment Different scenariosRecommendations Example Calculating the polarizationCard connector pinout RS485 schematic for the cardContact no. Signal SUB-DAtv71ModbusJbusENV1 2005-05