3.Press the Setup button. The CV RTU Zone Setup screen appears.
CV RTU 24 - Zone Setup
Thermostat Warm / Cool | Enabled | Heating Unocc Setpoint: | 62.0 Deg F |
Adjust: |
|
|
|
Temporary Occupancy | Enabled | Heating Occ Setpoint: | 68.0 Deg F |
Input: |
|
|
|
Control Mode: | Auto | Cooling Occ Setpoint: | 72.0 Deg F |
|
| Cooling Unocc Setpoint: | 78.0 Deg F |
Select value to modify.
Edit Zone Name | Zone Status | Instant | |
Shutdown | |||
|
|
Figure 43: CV RTU Zone Setup Screen
FIG:ZneStupCVRTU
4.Press the button for the zone parameter you want to change. The button label describes the current setting. When you press the button, the appropriate screen appears, allowing you to change the value. Table 16 lists these parameters and their ranges or possible selections.
Table 16: CV RTU Zone Setup Parameters
Parameter |
| Parameter Range/Selections | |
|
|
| |
Thermostat Warm/Cool Adjust |
| Enabled or Disabled | |
|
|
| |
Temporary Occupancy Input |
| Enabled or Disabled | |
|
|
| |
Control Mode |
| Auto, Heating, Cooling, Fan Only, Off | |
|
|
| |
Heating Unocc Setpoint |
| Valid range 55.0 to 68.0 Deg F1 | |
Heating Occ Setpoint |
| Valid range 62.0 to 72.0 Deg F1 | |
Cooling Occ Setpoint |
| Valid range 68.0 to 78.0 Deg F1 | |
Cooling Unocc Setpoint |
| Valid range 75.0 to 90.0 Deg F1 | |
|
|
|
|
1.Heating Unoccupied <= Heating Occupied <= Cooling Occupied <= Cooling Unoccupied
5.If you want to edit the name of the zone, press the Edit Zone Name button. On the Zone Name screen that appears, use the
6.After you complete the zone setup changes, press OK. The CV RTU Zone Setup screen returns, reflecting the changes you made.
System Manager/Zone Coordinator User’s Manual | 63 |