York YKSMU2x0-0, YK-ZCU4x0-0, YK-ZCU2x0-0 CV RTU 24 Zone Setup, CV RTU Zone Setup Parameters

Page 63

428516-YUM-B-0908

3.Press the Setup button. The CV RTU Zone Setup screen appears.

CV RTU 24 - Zone Setup

Thermostat Warm / Cool

Enabled

Heating Unocc Setpoint:

62.0 Deg F

Adjust:

 

 

 

Temporary Occupancy

Enabled

Heating Occ Setpoint:

68.0 Deg F

Input:

 

 

 

Control Mode:

Auto

Cooling Occ Setpoint:

72.0 Deg F

 

 

Cooling Unocc Setpoint:

78.0 Deg F

Select value to modify.

Edit Zone Name

Zone Status

Instant

Shutdown

 

 

Figure 43: CV RTU Zone Setup Screen

FIG:ZneStupCVRTU

4.Press the button for the zone parameter you want to change. The button label describes the current setting. When you press the button, the appropriate screen appears, allowing you to change the value. Table 16 lists these parameters and their ranges or possible selections.

Table 16: CV RTU Zone Setup Parameters

Parameter

 

Parameter Range/Selections

 

 

 

Thermostat Warm/Cool Adjust

 

Enabled or Disabled

 

 

 

Temporary Occupancy Input

 

Enabled or Disabled

 

 

 

Control Mode

 

Auto, Heating, Cooling, Fan Only, Off

 

 

 

Heating Unocc Setpoint

 

Valid range 55.0 to 68.0 Deg F1

Heating Occ Setpoint

 

Valid range 62.0 to 72.0 Deg F1

Cooling Occ Setpoint

 

Valid range 68.0 to 78.0 Deg F1

Cooling Unocc Setpoint

 

Valid range 75.0 to 90.0 Deg F1

 

 

 

 

1.Heating Unoccupied <= Heating Occupied <= Cooling Occupied <= Cooling Unoccupied

5.If you want to edit the name of the zone, press the Edit Zone Name button. On the Zone Name screen that appears, use the on-screen keyboard to enter a new name. Click OK to save.

6.After you complete the zone setup changes, press OK. The CV RTU Zone Setup screen returns, reflecting the changes you made.

System Manager/Zone Coordinator User’s Manual

63

Image 63
Contents User’s Manual System Manager/Zone Coordinator Zones, Groups, and Members Event Scheduling Basic ProceduresSetup Procedures Scheduling ProceduresZoning System Setup Procedures Alarm ProceduresSummary Procedures Zone Setup ProceduresDial-up Communication Procedures Auxiliary Points Setup ProceduresDocument Introduction System Manager/Zone Coordinator on the Network System Startup System ConfigurationLocal Controller Display Menu Structure System Manager/Coordinator Menu StructureScreen Layout ZC6 DetailsIcons on Main Selection Bar Navigation Area Title AreaMain Display Area Help Text/Paging Information AreaEnter Password Screen Three User Password LevelsEnter Operator password Home Screens Default Passwords ProvidedList of Default Passwords Contents of Home Screen DisplayDisplay and Navigation Screens YK-SMU-0 SetupSchedule 1 Mon Occupancy Time Data Entry ScreensRemote User Interface Specifying User Name and Password in BrowserTypes of Alarms Alarms and Alarm PrioritiesPagers Alarm DestinationsAlarm Detection Buffer LimitationTemporary Occupancy Override Zones, Groups, and MembersEvent Scheduling Text MessagesException Schedules Global and Instant ShutdownTrend Data Collection All Schedules Temporary OccupancyDisplay Units on User Interface Display UnitsMaintenance Procedures Basic Procedures Entering Your PasswordWaking up the Display Logging Off the Remote User Interface Logging On the Remote User InterfaceSetup Options Menu Structure Setup ProceduresSetting Date and Time Parameters Time ManagementTime Management Parameters Change Operator Password Changing the Administrator or Operator PasswordSecurity Password Enabling or Disabling Password SecurityRemote User Interface Enabling or Disabling the Remote User InterfaceSetting up a Modem Modem SetupModem Parameters Specifying Ethernet SettingsEthernet Parameters Ethernet SetupYK-SMU-0 Display Setup Selecting Display UnitsCalibrating the Display Calibrate Screen System Manager Name Specifying System Manager/Zone Coordinator NameJob Name Entering Job NameScheduling Procedures Schedule Options Menu Structures Adding a Schedule Schedule 1 Daily SchedulesExample Schedules Screen for Monday Schedule 1 Schedule MonDelete Schedule Screen Deleting a ScheduleAdding a Member to a Schedule Select New Member for ScheduleDeleting a Member from a Schedule Schedule 1 Member ListProperties for Exception May 15, 2008 through May 15 Adding an Exception ScheduleProperties for Exception Definition Screen Setting up Temporary Occupancy TimeTemporary Occupancy Time Beginning Temporary Occupancy of a ScheduleBeginning or Ending Temporary Occupancy to All Schedules Ending Temporary Occupancy of a ScheduleAlarm Options Menu Structure Alarm ProceduresPager Setup Configuring Pager as Alarm DestinationPager Setup Parameters Part 1 Email Setup Pager Setup Parameters Part 2Configuring E-mail Account as Alarm Destination Configuring Text Message as Alarm Destination Mail Destination Setup ParametersText Message Setup Parameters Part 1 Text Message SetupSetting Alarm Indicators Text Message Setup Parameters Part 2Alarm Priorities that Activate Alarm Indicators Alarm Priorities That Activate Alarm Indicators ScreenViewing an Alarm Summary YK-SMU-10 AlarmsAlarms Detail Screen Deleting One or All AlarmsSummary Options Menu Structure Summary ProceduresViewing System Summaries YK-SMU-10 SummaryViewing Trend Data ZC6 Zone Temperature Trend Zone Setup Options Menu Structure Zone Setup ProceduresSetting Up a Changeover Bypass Zone ZC6 Zone SetupSetting Up a CV RTU Zone Zone Setup ParametersCV RTU Zone Setup Parameters CV RTU 24 Zone SetupSetting up a VAV RTU Zone VAV 24 Zone SetupVAV RTU Zone Setup Parameters Zone Name Editing a Zone NameViewing Zone Status ZC6 Zone StatusCopying Zone Setup to All Zones Instant Shutdown of All Systems Requesting Global Shutdown of all Zones in all SystemsViewing Device Diagnostics CV RTU1 DiagnosticZoning System Setup Options Menu Structure Zoning System Setup ProceduresSetting Up a Zoning System YK-ZCU Zoning System SetupZoning System Setup Parameters VAV RTU Zoning System Setup ParametersViewing Zoning System Status YK-ZCU Zoning System StatusInstant Shutdown of CV RTU24 Requesting Instant Shutdown of a Zoning SystemBalancing a Zoning System Balance ModeAuxiliary Points Setup Options Menu Structure Auxiliary Points Setup ProceduresSetting up Auxiliary Points IOM Points Setup Selections Part 1IOM-1 Auxiliary Points Selection BO4 IOM Points Setup Selections Part 2IOM Name Editing an IOM Controller NameViewing Auxiliary Points Status IOM-1 Auxiliary Points DetailsViewing IOM Controller Point Trend Data AI1 TrendCreating a Dial-up Connection Dial-up Communication ProceduresGetting Ready Window Connection Name Window Connection Availability Window Completing the New Connection Wizard New Connection Window Connection Window Dialing up a System Manager or CoordinatorMaintenance Options Menu Structure YK-SMU-0 Backup to USB Flash Drive Backing up Current ConfigurationYK-SMU-0 Restore from USB Flash Drive Restoring Configuration InformationRestore Confirmation Screen System Manager YK-SMU-0 Restore Factory Defaults Restoring Factory SettingsYK-SMU-0 Relearn Connected Devices Relearning Connected DevicesRestarting the System Manager/Zone Coordinator