Zone Setup Procedures
Zone setup procedures include:
•Setting up a zone
•Editing zone name
•Viewing zone status
•Copying zone setup to all zones
•Requesting global shutdown of all zones
•Viewing device diagnostics for a zone
Figure 41 is a flowchart of the menu structure that is used to set up zones on the Sys- tem Manager. These menu selections are described in the sections that follow.
Setup
Systems
CV RTU
Zone
Coordinator
Coordinator Setup
and Status
System
Status
Zoning System
Status
Setup |
Balance System |
Instant |
Shutdown |
• Control Mode | CV/COB RTU |
•Discharge Cooling Setpoint
•Discharge Heating Setpoint
•Min Number of Requests to Change Mode
•Min Number of Urgent Requests to Change Mode
•Min Time Before Changeover
•Number of Cooling Stages
•Number of Heating Stages
•Static Pressure Setpoint
• Control Mode | VAV RTU |
•Discharge Air Temp Setpoint
•Discharge Air Temp Strategy
•Duct Static Setpoint
•Duct Static Setpoint Reset
•Duct Static Shutdown Limit
•Econ Damper Position for Exhaust Fan On
•Econ Damper Position for Exhaust Fan On
•Economizer Min Position
•Max DAT Setpoint Adjust
•Max Duct Static Setpoint Adjust
•Morning
•Morning
•Representative Zone
•Unoccupied Heating/Cooling
FIG:ZneSysStupFlw
Figure 41: Zone Setup Options - Menu Structure
60 | System Manager/Zone Coordinator User’s Manual |