Seagate FR-A7AY instruction manual Extension Analog Output Function Parameter List

Page 19

EXTENSION ANALOG OUTPUT

4.4 Extension Analog Output Function Parameter List

Parameter

Name

Setting Range

Minimum

Initial

Number

Increments

Value

 

 

1 to 3, 5, 6, 8,

 

 

306

Analog output signal selection

(9), 10 to 14, 17,

1

2

 

 

21, 24, 50, 52, 53

 

 

307

Setting for zero analog output

0 to 100%

0.1

0%

308

Setting for maximum analog output

0 to 100%

0.1

100%

309

Analog output signal voltage/current

0, 1, 10, 11

1

0

switchover

 

 

 

 

 

 

1 to 3 , 5, 6, 8,

 

 

310

Analog meter voltage output

(9), 10 to 14, 17,

1

2

 

 

21, 24, 50, 52, 53

 

 

311

Setting for zero analog meter

0 to 100%

0.1

0%

voltage output

 

 

 

 

312

Setting for maximum analog meter

0 to 100%

0.1

100%

voltage output

 

 

 

 

323

AM0 0V adjustment

900 to 1100%

1

1000%

324

AM1 0mA adjustment

900 to 1100%

1

1000%

C0(900)

FM terminal calibration

C1(901)

AM terminal calibration

REMARKS

For Pr. 306 and Pr. 310, write is enabled even when "0" is set in Pr. 77.

14

Image 19
Contents FR-A7AY Safety Instructions This section is specifically about Safety mattersInjury Prevention  Contents  Digital Output Unpacking and Product Confirmation PRE-OPERATION InstructionsPacking confirmation Terminal layout PartsFront view Rear viewOutput signals SpecificationsMemo Pre-Installation Instructions Installation and WiringRemove the inverter front cover Installation ProcedureTightening Torque Cable Size Wiring30K or less 37K or more Parameter List Name Setting Range Minimum Initial Refer to NumberValue Parameter List Extension Analog Output Wiring ExampleInternal Block Diagram Terminals Terminal Symbol Terminal Name DescriptionExtension Analog Output Function Parameter List Parameter Name Setting Range Minimum Initial NumberSetting Adjustment ProcedureStart Calibration of meterExtension Analog Output Types of Monitor Increments Full-Scale Value Output signal settingWhen Pr = 0 When Pr = 10 Analog signal adjustment Pr , Pr , Pr , PrInstructions Digital Output Digital Output Digital Output Function Parameter List Name Initial Value Setting RangeFunction Output Signal ListSetting Function SettingRO2 Print Date Manual Number Revision Revisions